Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 51

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
Info
Insert a NEW
USER
password
0000
Evolution+
Code
ME 28.00 EN
HW
pCO5+S
NAND
50MB
Flash 2MB + 7MB + 4MB
Ram
2048KB
Boot 05.01
Bios06.21
Historical
Filter
for alarm event:
Location:
ALL
15:32:28
11/05/12
pLAN Address: 01
Event n° 004
SET A002
Type:AUTO
Wrong Power Phases
Sequence
Location
:PLANT
Action
:UNIT
In/Out
DIGITAL INPUT STATUS:
ID1
ID8
ID2
ID3
ID4
ID5
ID6
ID7
Technical manual
Description
Access mask to Info menu.
Press "Up" or "Down" to scroll through the other masks and "Esc" to return to the menu selection list.
Submenu that can be used to change user password and display software info.
Sets a new "User" password.
Warning: the value set in this field is the one and only to access the "User" menu.
This mask contains the reference information of the software [Code ME 28.00 EN].
The closed padlock symbol shows that the board is provided with its propriety software.
The second part of the mask shows information about the hardware: size (S), memories (NAND, Flash, Ram) and
the versions of the installed operating system (boot and bios).
Access mask to Alarms Log menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
Mask selecting the alarm type from the display history. It is possible to select from COMPRESSOR, CIRCUIT,
UNIT, and SYSTEM alarms. For a description of the location field, please refer to the "EVENTS" chapter
Mask displaying the event history. Each event recorded contains the following details:
Date and time
Unit pLAN address (if there is a LAN controller network)
Event number
Engagement or disengagement event (SET, RESET)
Event code
Type of reset (AUTO, MANUAL)
Event description
Event localisation (COMPR, CIRCUIT, UNIT, PLANT)
Type of event block action (COMPR, CIRC, UNIT, CW, HU, EH, FN)
Access mask to In/Out menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.
Displays the status of the digital inputs. The number of displayed inputs depends on the unit type.
For the meaning of each digital input, please refer to the "input/output configuration tables"
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
51
N. Par.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S-mext-g00 044

Table of Contents