Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 42

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
--------------- P30.02
BMS Address:
011
--------------- P30.03
BMS protocol config.:
ModBus
--------------- P30.04
BMS baud rate config.:
19200
--------------- P30.05
ON/OFF by BMS status:
N
--------------- P30.09
Enable T.regulation
from Supervisor:
--------------- P30.11
Enable FC STOP by
supervisor:
GSM modem management
Modem password
1234
Maximum numbers in
address book:
GSM modem management
Address book
position:
Phone Number:
432100
GSM modem management
SMS message text:
**test messaggio **
GSM modem management
SMS sending fuction
status:
Technical manual
Description
Parameters for configuring the BMS address and
protocol (0:Standard - 1:Modbus - 2:GSM Modem - 3:LON - 4:Bacnet - 5:TCP/IP - 6:WinLoad)
BMS baud rate configuration parameter (0:1200 - 1:2400 - 2:4800 - 3:9600 - 4:19200)
Parameters to configure ON/OFF from BMS (N:disabled - Y:enabled)
and, in case of cooled water unit, to change the Summer/Winter mode from BMS (N:disabled - Y:enabled)
Parameter for enabling adjustment according to the temperature provided by BMS (N: disabled - Y: enabled)
N
Enable stopping of Freecooling from BMS
Visible only on unit with Direct Freecooling
N
GSM modem management. Requests modem password
4
Select a telephone number from the list
2
Insert message text. Digit 1 – Digit 60 SMS message text (numbers and letters)
SMS forwarding function status
N
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
42
N. Par.
30.02
30.03
30.04
30.05
30.09
30.11

Hide quick links: