Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 53

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
--------------- P50.07
Set point dehumdif. by
LAN limits:
75%RH
--------------- P50.08
Set point humdif. by
LAN limits:
35%RH
--------------- P50.09
MIN room temperature
for deumid OFF: 23.0°C
Unit
INTERNAL FAN
Speed:
100%
Regulation Type:
STANDARD
24.0 °C
15.0 °C
35.0 °
AUXILIARY T-H PROBE
Addr. 129
24.0 °C
50.0 %
Status:Offline
REGULATION RAMP:
Cooling
ramp: 000.0
Heating
ramp: 000.0
Post Heat
ramp: 000.0
FC damper
ramp: 000.0
SAFETY REDUCTION LOAD
NORMAL WORK
Technical manual
Description
Parameters for setting
Dehumidification setpoint for LAN limits
Humidification setpoint for LAN limits
Parameter for setting the minimum room temperature for dehumidifier off
Access mask to unit menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the submenu.
Mask that displays the speed of the internal fans and type of adjustment
Active probe value display mask
Return temperature probe
Delivery temperature probe
External temperature probe
Mask that displays the value of the serial auxiliary probe (address 129).
Visible if the probe is configured
Regulation ramp punctual value reading.
Mask that displays the status of the Safety Reduction Load function
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
53
N. Par.
50.07