Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 47

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
Alarm out
2
--------------- P33.15
(188)Offline
PAC-IF013B-E Master
add. 21 al out
addressing:
A
--------------- P33.16
(810)PAC-IF013B-E
Master P1 alarm
out addressing:
A
--------------- P33.17
(811)PAC-IF013B-E
Master P2 alarm
out addressing:
A
--------------- P33.18
(812)PAC-IF013B-E
Master P6 Freezing
al out addressing:A
--------------- P33.19
(813)PAC-IF013B-E
Master P6 Overheating
al out addressing:A
--------------- P33.20
(814)PAC-IF013B-E
Master P9 alarm
out addressing:
A
--------------- P33.21
(815)PAC-IF013B-E
Master E0/E4 alarm
out addressing:
A
--------------- P33.22
(816)PAC-IF013B-E
Master E1 alarm
out addressing:
A
Technical manual
Description
Access mask to "Alarm out 2" submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
PAC-IF013B-E Master offline alarm addressing on digital output (0:A - 1:none - 2:B)
P1 PAC-IF013B-E Master alarm addressing on digital output (0:A - 1:none - 2:B)
P2 PAC-IF013B-E Master alarm addressing on digital output (0:A - 1:none - 2:B)
P6 Freezing PAC-IF013B-E Master alarm addressing on digital output (0:A - 1:none - 2:B)
P6 Overheating PAC-IF013B-E Master alarm addressing on digital output (0:A - 1:none - 2:B)
P9 PAC-IF013B-E Master alarm addressing on digital output (0:A - 1:none - 2:B)
E0/E4 PAC-IF013B-E Master alarm addressing on digital output (0:A - 1:none - 2:B)
E1 PAC-IF013B-E Master alarm addressing on digital output (0:A - 1:none - 2:B)
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
47
N. Par.
33.15
33.16
33.17
33.18
33.19
33.20
33.21
33.22