Fieldbus 2; Master Pac-If013Be Interface Card Communication Configuration - Mitsubishi Electric s-MEXT-G00 006 Technical Manual

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
19.2

FIELDBUS 2

The following devices are connected to the FieldBus 2 port on the controller:
Module
Modbus address
Master PAC-IF013B-E
21
Slave 1 PAC-IF013B-E
22
19.2.1

Master PAC-IF013BE interface card communication configuration

The configuration of the communication parameters for the Master PAC-IF013B-E interface card is completed using the Dip Switches of the electronic cards.
Master PAC-IF013B-E card configuration (address 21)
Dip-switches
SW6: 1÷2
SW1: 1÷3
SW1: 8
SW3: 6÷7
SW3: 8
SW4: 1
SW4: 2
SW4: 3
SW4: 4
SW4: 5
SW4: 6
SW4: 7
SW4: 8
Nessuno
Slave 1 PAC-IF013B-E card configuration (address 22)
Dip Switch
SW6: 1÷2
SW1: 1÷3
SW1: 8
SW3: 6÷7
SW3: 8
SW4: 1
SW4: 2
SW4: 3
SW4: 4
SW4: 5
SW4: 6
SW4: 7
SW4: 8
Nessuno
Technical manual
Method for changing address
Dip switch
Dip switch
Description
Protocol
Baud Rate
Device address
Parity type
Stop bits
Data length
Description
Protocol
Baud Rate
Device address
Parity type
Stop bits
Data length
106
Position
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON
-
Position
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
-
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
Value
Manual step control through the Modbus
protocol
with IMOUC
with IMOUC
disabled (single Mr
enabled
Slim unit)
(multiple Mr Slim
unit)
19200
21
NONE
2 bit
8 bit
Value
Manual step control through the Modbus
protocol with IMOUC enabled
19200
22
NONE
2 bit
8 bit

Hide quick links: