Expansion No. 1 (Address 8) - Mitsubishi Electric s-MEXT-G00 006 Technical Manual

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
17.2

EXPANSION NO. 1 (ADDRESS 8)

s-MEXT-G00
Connector
Type
Description
Air differential pressure transducer
4-20mA
B1
As an alternative: Delivery air temperature from
0-5V
DC
J9
superv.
B2
Free
B3
NTC
External Air Temperature
J10
B4
Free
Free
2
Connector
Type
Description
ID1
/
Internal electronic fan 1 alarm
ID2
/
Internal electronic fan 2 alarm
J4
ID3
Free
ID4
Free
Free
2
Analogue Outputs
Connector
Type
Description
J2
Y1
0-10V
Direct Freecooling damper
DC
Free
0
Connector
Type
Description
NO1
J5
/
Direct OPEN FC
NC1
NO2
J6
Free
NC2
NO3
J7
Free
NC3
NO4
J8
Free
NC4
Free
3
Notes:
(2) Only with fan ADL function enabled (P23.71)
Technical manual
Analogue Inputs
Digital Inputs
(2)
(2)
Digital Outputs
TRANSLATION OF THE ORIGINAL INSTRUCTIONS