Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 43

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
GSM modem management
Send SMS Test:
Hang Up:
Alarm out
--------------- P31.01
Alarm out A logic: _\_
--------------- P31.02
Alarm out B logic: _\_
--------------- P31.03
(003) Fire/smoke alarm
out addressing:A
--------------- P31.04
(004) Phase seq. alarm
out addressing:A
--------------- P31.10
(101) Air flow alarm
out addressing:A
--------------- P31.11
(120) Room temp. probe
alarm out addressing:
A
--------------- P31.12
(125) Ambient humidity
probe alarm
out addressing:A
--------------- P31.13
(130) Diff. pressure
probe alarm
out addressing:A
Technical manual
Description
Text SMS sending mask.
N
N
Access mask to "Alarm out" submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
Parameters to configure the alarm A contact status (0:NO - 1:NC)
and the alarm B contact status (0:NO - 1:NC)
Fire/smoke alarm addressing on digital output (0:A - 1:none - 2:B)
Phase sequence alarm addressing on digital output (0:A - 1:none - 2:B)
Air Flow alarm addressing on digital output (0:A - 1:none - 2:B)
Ambient air temperature probe alarm addressing on digital output (0:A - 1:none - 2:B)
Ambient humidity probe alarm addressing on digital output (0:A - 1:none - 2:B)
Differential pressure probe alarm addressing on digital output (0:A - 1:none - 2:B)
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
43
N. Par.
31.01
31.02
31.03
31.04
31.10
31.11
31.12
31.13