Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 39

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
Manual Set
000000
000002
000000
Humidity/temperature
simulation enabling: Y
Ambient temperature
simulation:
24.0°C
Ambient humidity
simulation:
50.0 %RH
Force rotation pLAN
Force:N
Time to next:00000sec
Optional
--------------- P27.02
Config heater:
N
--------------- P27.03
Electric heater type:
ON-OFF
--------------- P27.04
Humidity sensor:
N
--------------- P27.05
Humidifier:
Disabled
--------------- P27.06
Humidif. config
001-1 kg/h Reduct 200V
1-ph Drain Pump
Confirm change:
Y
--------------- P27.07
Max steam production:
100%
Technical manual
Description
Reset number of heater and humidifier starts and manual setting of the times at which to start
Mask for simulating the presence of the temperature/humidity probe and relative set temperature value
Mask for selecting simulated humidity value
Mask for manual forcing of pLAN rotation
Only visible for Master units when the pLAN is configured and rotation is active
Access mask to the Optional submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
Electric heater configuration (N:disabled - Y:enabled).
Configuration type Electric heating elements (0:ON/OFF - 1:Modulating heating element)
Hot gas valve configuration (N:disabled - Y:enabled)
Humidifier configuration (0:disabled - 1:internal)
Mask for configuring the internal humidifier model (cylinder type). Choice of the cylinder and confirmation of the
chosen cylinder.
Visible only if the humidifier is internal.
Parameter for selecting Maximum steam production from 0 to 100 % if an internal humidifier is present.
Visible only if the humidifier is internal.
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
39