Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 27

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
Safety 2
Safety 2 parameter
NOT Available
Default
Default Setup
N
Reset Historical
Alarm
N
Service
Password:
0000
Regulations
--------------- P20.01
Regulat. probe choice:
Delivery Temp
--------------- P20.02
Fan delay from
power-on:
000s
--------------- P20.03
Fan modulation delay:
120s
--------------- P20.04
Fan regulation delay:
050s
Technical manual
Description
Mask confirming access to the Protections 2 submenu. Press "Up" or "Down" to scroll the other masks and "Esc"
to return to the submenu.
It informs that no parameters are available in the menu for the unit
Access mask to initialisation menu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
This restores the default values.
Deletes the memory and installs "logical" values.
The chiller must then be programmed with the parameter set during factory testing. The mask is not displayed
when the chiller is ON.
Deletes the contents of the alarms log on the display
Access mask to Service menu Enter the "Service" password for access. This menu must be accessed only by
authorised personnel.
Access mask to the Regulation submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to
the submenu.
Parameter for configuring the type of regulation probe (0:return - 1:delivery)
and parameter for configuring the fan start delay from power on
Parameter for setting the fan modulation start delay
and the fan adjustment start delay.
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
27
N. Par.
20.01
20.02
20.03
20.04