Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
99.9 99.9 99.9
99.9 99.9 99.9
99.9 99.9 99.9
99.9LAN:Local Unit
Temp.(°C)
LAN 1: 2: 3:
4: 5: 6:
7: 8: 9:
10:
01 LAN APL
Current 0020 Pa
Target
0020 Pa
APL 0020 Pa
Local 0019 Pa
Status
On target
DT 03.0
T.INT
T.EXT
24.0
21.0
Status Enabled
Position ALL INTERNAL
000%
000.0kg/h
A 00.0
µS/cm000
Alarm
Warning
code:00
code:0
Energy Managment
Voltages (V) 000
Current (A)
000.0
Active Power(kW)0000.0
Energy Managment
Voltages (V)
L1-L2
000
L2-L3
000
L3-L1
000
Neutral 1
000
Neutral 2
000
Neutral 3
000
Energy Managment
Current (A)
Line 1
000.0
Line 2
000.0
Line 3
000.0
Neutral
000.0
Energy Managment
Active Power (kW)
Phase 1
0000.0
Phase 2
0000.0
Phase 3
0000.0
Total
0000.0
Technical manual
Description
Mask that displays all the temperature values read by the units on the LAN network. This mask is displayed only at the Master unit
(pLAN address=1).
Visible if the pLAN is configured
Local network (LAN) status display mask. This mask is displayed only in the Slave unit (LAN address=2÷10).
Visible if the local network (LAN) is configured
Unit operating
Unit not operating
APL pLAN function operation status display mask. This mask is displayed for all the units (pLAN address=1 to 10).
Visible if the pLAN is configured and the APL function is active
Direct Free Cooling function operation display mask.
Visible only if the function is enabled
It shows:
Internal temperature, external temperature, Freecooling enable, damper position (internal only, mix, external only) and its opening
percentage. The image graphically describes the Free Cooling damper position:
Humidifier operation status display mask.
Visible if humidifier is present
Display mask for the values detected by the network transducer in case on mono-phase circuit.
Visible if the network transducer is present and configured
Display mask for the electric values detected by the network transducer. Displays phase-phase and phase voltage (phase-
neutral) values.
Only for three-phase units.
Visible if the network transducer is present and configured
Display mask for the electric values detected by the network transducer. Displays phase and neutral current.
Only for three-phase units.
Visible if the network transducer is present and configured
Display mask for the electric values detected by the network transducer. The phase active power is displayed
Only for three-phase units.
Visible if the network transducer is present and configured
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
18