Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 44

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
--------------- P31.14
(140) Air delivery
temp. probe alarm out
addressing:
A
--------------- P31.16
(144) Outdoor air temp
probe alarm
out addressing:A
--------------- P31.18
(150) El Heaters alarm
out addressing:
-------------- P31.19
(180)Probe T-H offline
alarm out addressing:
A
-------------- P31.23
(192)exp offline alarm
out addressing: A
-------------- P31.24
(199)Transd. offline
alarm out addressing:
A
--------------- P31.25
(195) Humidifier
Offline
out addressing:A
--------------- P31.42
(402) Life timer
expired
out addressing: A
--------------- P31.43
(404) Humidifier Drain
alarm
out addressing: A
--------------- P31.44
(406) Humidif no water
alarm
out addressing: A
Technical manual
Description
Delivery air temperature probe alarm address on digital output (0:A - 1:none - 2:B)
External air temperature probe alarm addressing on digital output (0:A - 1:none - 2:B)
Electric heater alarm addressing on digital output (0:A - 1:none - 2:B)
A
T+H probe offline alarm addressing on digital output (0:A - 1:none - 2:B)
Inverter IO expansion offline alarm addressing on digital output (0:A - 1:none - 2:B)
Network transducer offline alarm addressing on digital output (0:A - 1:none - 2:B)
Humidifier CPY module alarm addressing (0:A - 1:none - 2:B)
Humidifier life expired alarm addressing on digital output (0:A - 1:none - 2:B)
Humidifier discharge alarm addressing on digital output (0:A - 1:none - 2:B)
Humidifier insufficient water alarm addressing on digital output (0:A - 1:none - 2:B)
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
44
N. Par.
31.14
31.16
31.18
31.19
31.23
31.24
31.25
31.42
31.43
31.44