Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 26

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
Mask of the terminal
Compressor
--------------- P12.01
MIN time ON comp.:
180s
--------------- P12.02
MIN time OFF comp.:
180s
--------------- P12.03
MIN time ON-ON:
same compressor:
360s
Valve
--------------- P13.05
EEV status:
N
Safety
--------------- P14.03
Probe
alarm delay time: 060s
--------------- P14.04
Low Pressure
alarm delay time: 180s
--------------- P14.08
Cooling set point
lower limit:
10.0°C
--------------- P14.14
Max t. for man. test:
1800s
Technical manual
Description
Access mask to Compressors submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
Parameters for setting
Minimum compressor ON time
Minimum compressor OFF time
Parameters for setting
Minimum time between two ON's of the same compressor
Access mask to valves submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to return to the
submenu.
Parameters for setting the electronic valve (N:disabled - Y:enabled)
Mask confirming access to the Protections submenu. Press "Up" or "Down" to scroll the other masks and "Esc" to
return to the submenu.
Parameters for setting
Sensors alarm delay
Low pressure alarm delay
Parameters for setting the Manufacturer lower limit cooling setpoint
Parameters for setting
Maximum manual operation time
Maximum manual electronic valve operation time
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
26
N. Par.
12.01
12.02
12.03
13.05
14.03
14.04
14.08
14.14
14.15