Procedure
1. Set the DIP switch for analog input 0 on the Control Unit to current input ("I").
2. set p0756[0] = 3
You have defined analog input 0 as a current input with wire-break monitoring.
3. Set p0757[0] = 6.0 (x1)
4. Set p0758[0] = -100.0 (y1)
5. Set p0759[0] = 12.0 (x2)
6. Set p0760[0] = 100.0 (y2)
7. Set p0761[0] = 6
An input current < 6 mA results in fault F03505.
The characteristic for the application example is set.
Parameters
Parameter
p0757[0...n]
p0758[0...n]
p0759[0...n]
p0760[0...n]
p0761[0...n]
p0762[0...n]
8.4.7

Setting the deadband

Function description
With the control enabled, electromagnetic interference on the signal cable can cause the motor
to slowly rotate in one direction in spite of a speed setpoint = 0.
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
Description
CU analog inputs characteristic value x1
CU analog inputs characteristic value y1
CU analog inputs characteristic value x2
CU analog inputs characteristic value y2
CU analog inputs wire-break monitoring, response
threshold
CU analog inputs wire breakage monitoring time
8.4 Adapt the default setting of the terminal strip
Factory setting
0
0%
10
100%
2
100 ms
Advanced commissioning
129