Siemens SINAMICS G120D Operating Instructions Manual page 44

Distributed inverter cu240d-2 control unit with encoder evaluation
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Installation
4.2 Electrical Installation
Table 4-4
Rated power
0.75 kW
1.5 kW
3 kW
4 kW
5.5 kW
7.5 kW
Table 4-5
Branch circuit protection according to UL Categories DIVQ and NKJH
Rated
Power Module
power
0.75 kW
6SL3525-0PE17-5AA1
1.5 kW
6SL3525-0PE21-5AA1
3 kW
6SL3525-0PE23-0AA1
4 kW
6SL3525-0PE24-0AA1
42
Branch circuit protection with non-semiconductor fuses of Classes J, T, CC, G or CF (UL
Category JDDZ)
Power Module
6SL3525-0PE17-5AA1
6SL3525-0PE21-5AA1
6SL3525-0PE23-0AA1
6SL3525-0PE24-0AA1
6SL3525-0PE25-5AA1
6SL3525-0PE27-5AA1
Fram
Article No.
e size
FSA
3RV2711...
3RV1742..., LGG... or
CED6...
3RV2021-1JA...
FSA
3RV2711...
3RV1742..., LGG... or
CED6...
3RV2021-1JA...
FSB
3RV1742..., LGG... or
CED6...
3RV2721...
3RV2021-4AA...
3RV1031-4AA... or
3RV2031-4AA...
FSC
3RV1742...
LGG... or CED6...
3RV2021-4BA...
3RV1031-4BA... or
3RV2031-4BA...
Frame
Max. rated current
size
of the fuse
FSA
10 A
15 A
FSB
25 A
FSC
35 A
45 A
60 A
UL cat.
Max. rated cur‐
rent of the cir‐
cuit breaker
DIVQ
15 A
DIVQ
15 A
NKJH
10 A
DIVQ
15 A
DIVQ
15 A
NKJH
10 A
DIVQ
25 A
DIVQ
22 A
NKJH
16 A
NKJH
16 A
DIVQ
35 A
DIVQ
35 A
NKJH
20 A
NKJH
20 A
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
Short circuit current rat‐
ing SCCR
100 kA, 480 V 3 AC
100 kA, 480 V 3 AC
100 kA, 480 V 3 AC
100 kA, 480 V 3 AC
100 kA, 480 V 3 AC
100 kA, 480 V 3 AC
Short circuit cur‐
rent rating SCCR
65 kA, 480Y/277 V
AC
65 kA, 480 V 3 AC
65 kA, 480Y/277 V
AC
65 kA, 480Y/277 V
AC
65 kA, 480 V 3 AC
65 kA, 480Y/277 V
AC
65 kA, 480 V 3 AC
50 kA, 480Y/
277 V AC
65 kA, 480Y/277 V
AC
65 kA, 480Y/277 V
AC
65 kA, 480Y/277 V
AC
65 kA, 480 V 3 AC
65 kA, 480Y/277 V
AC
65 kA, 480Y/277 V
AC

Advertisement