8.4.7
Setting the deadband
Function description
Figure 8-5
With the control enabled, electromagnetic interference on the signal cable can cause the
motor to slowly rotate in one direction, in spite of a speed setpoint = 0.
The deadband acts on the zero crossover of the analog input characteristic. Internally, the
converter sets its speed setpoint = 0, even if the signal at the analog input terminals is slightly
positive or negative. This prevents the converter from rotating the motor when the speed
setpoint = 0.
Parameter
Parameter
p0764[0]
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
Deadband of the analog input
Description
Analog inputs deadband, AI 0
8.4 Adapt the default setting of the terminal strip
Factory setting
0
Advanced commissioning
197