11.2

Performance ratings Power Module

Performance ratings
Table 11-2
Feature
Line voltage & power
ranges
Line specification
Output voltage
Input frequency
Output frequency
cos φ
Converter efficiency
Overload capability (HO)
Inrush current
Pulse frequency
Electromagnetic compati‐
bility
Protection level
Temperature range
Storage temperature
Humidity
Operational altitude
Protection features
Standards
CE mark
Brake voltage
Standby current
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
Power Module performance ratings
Specification
3 AC 380 V ... 500 V ± 10 %
High Overload: 0.75 kW ... 7.5 kW (1.0 hp ... 10.0 hp)
Relative short-circuit voltage of a transformer u
The specification only refers to the total instantaneous regenerative feed‐
back, however not to the total connected power of all of the power modules
connected to the same transformer.
3 AC 0 V ... line volage × 0.87 (max.)
47 Hz ... 63 Hz
0 Hz ... 240 Hz
1.05
95 % ... 97 %
2 x Nominal output current for 3 seconds followed by 1.5 x Nominal output
current for 57 seconds every 300 seconds
Less than rated input current
4 kHz (standard); 4 kHz ... 16 kHz (in 2 kHz steps)
Internal Class A filters according to EN 55011
IP65 (when Power Module and Control Unit is fully assembled)
Standard CU: -10 °C ... +40 °C (14 °F ... 104 °F) - High Overload (HO)
Fail-Safe CU: 0 °C ... +40 °C (32 °F ... 104 °F) - High Overload (HO)
-40 °C ... +70 °C (-40 °F ... 158 °F)
< 95% RH - non-condensing
Up to 1000 m (3280 ft) above sea level without derating
Undervoltage, Overvoltage, Overload, Ground faults, Short circuit, Stall pre‐
vention, Motor blocking protection, Motor overtemperature, Power Module
overtemperature, Parameter interlock
UL, cUL, CE, C-tick
Conformity with EC Low Voltage Directive 73/23/EEC and filtered versions
also Electromagnetic Compatibility Directive 89/336/EEC
180 V DC (400 V half-wave rectified) 1 A maximum
The UL approved current rating for the brake output is 600 mA.
If the converter is powered-up, but the motor is still switched off, the con‐
verter requires a standby current.
You have to consider the standby current when calculating the size of the
conductors and selecting the correct protective devices on the line supply.
11.2 Performance ratings Power Module
≤ 1%
k
Technical data
331