You have downgraded the converter firmware to an older version.
10.5.5

Correcting a failed firmware upgrade or downgrade

How does the converter report a failed upgrade or downgrade?
The converter signals a failed firmware upgrade or down‐
grade with a quickly flashing RDY LED and a lit up BF LED.
Correcting a failed upgrade or downgrade
To correct a failed firmware upgrade or downgrade you can check the following:
• Does the firmware version fulfill the requirements of your converter?
– For an upgrade at least V4.5.
– For a downgrade at least V4.6.
• Have you inserted the card properly?
• Does the card contain the correct firmware?
• Repeat the appropriate procedure.
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
If the memory card is still inserted, depending on the previous content of the memory card,
one of the two following cases has occurred:
• The memory card contained a data backup: ⇒ The converter has taken over the settings
from the memory card.
• There was no data backup on the memory card: ⇒ The converter has the factory set‐
tings.
If the memory card did not contain a data backup of the converter settings, then you must
transfer your settings to the converter from another data backup.
Downloading the converter settings (Page 308).