Siemens SINAMICS G120D Operating Instructions Manual page 317

Distributed inverter cu240d-2 control unit with encoder evaluation
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

3. Connect Startdrive online with the drive.
The converter signals faults after the download. Ignore these faults, as they will be
automatically acknowledged by the following steps.
4. Press the "Start safety commissioning" button.
5. Enter the password for the safety functions.
6. Press the "End safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the converter power supply.
10.Wait until all LEDs on the converter are dark.
11.Switch on the converter power supply again.
12.Perform a reduced acceptance test.
(Page 326)
You transferred the settings from the PC to the new converter.
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
Reduced acceptance test after component replacement and firmware change
Corrective maintenance
10.3 Downloading the converter settings
315

Advertisement

Table of Contents
loading

Table of Contents