Advanced commissioning
8.4 Adapt the default setting of the terminal strip
Example
To output the fault message via digital output DO 1, you must connect DO 1 with the fault
message: Set p0731 = 52.3.
Parameter
Table 8-4
Parameter
r0052[0...15] CO/BO: Status word 1
r0053[0...11] CO/BO: Status word 2
A complete list of the binector inputs is provided in the List Manual.
Further information
You can invert the digital output signal using parameter p0748.
Additional information is provided in the parameter list and in function diagram 2241.
126
52.3
r0052.3
2
1
5
3
4
Binector outputs of the converter (selection)
Description
.00
1 signal: Ready for switching on
.01
1 signal: Ready for operation
.02
1 signal: Operation enabled
.03
1 signal: Fault active: The converter inverts signal
r0052.03 if it is interconnected to a digital output.
.04
0 signal: OFF2 active
.05
0 signal: OFF3 active
.06
1 signal: Switching on inhibited active
.07
1 signal: Alarm active
.08
0 signal: Deviation, setpoint/actual speed
.09
1 signal: Control request
.10
1 signal: Maximum speed (p1082) reached
.11
0 signal: I, M, P limit reached
.13
0 signal: Alarm, motor overtemperature
.14
1 signal: Motor clockwise rotation
.15
0 signal: Alarm, converter overload
.00
1 signal: DC braking active
.02
1 signal: Speed > minimum speed (p1080)
.06
1 signal: Speed ≥ setpoint speed (r1119)
Overview of the manuals (Page 361)
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
Factory setting
-
-