Technical data
11.8 Electromagnetic Compatibility
The immunity requirements apply equally to both filtered and unfiltered converters.
Table 11-8
EMC Phenomenon
Electrostatic Discharge (ESD)
Radio-frequency Electromagnet‐
ic Field
Amplitude modulated
Fast Transient Bursts
Surge Voltage
1.2/50 μs
Conducted
Radio-frequency Common Mode
Mains Interruptions & Voltage
Dips
Voltage Distortion
Voltage Unbalance
Frequency Variation
Commutation Notches
340
EMC Immunity
Standard
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
EN 61000-2-4
EN 61000-2-4
EN 61000-2-4
EN 60146-1-1
Level
4 kV Contact discharge
8 kV Air discharge
80 MHz ... 1000 MHz
10 V/m
80 % AM at 1 kHz
2 kV @ 5 kHz
1 kV differential (L-L)
2 kV common (L-E)
0.15 MHz ... 80 MHz
10 V/rms
80 % AM at 1 kHz
95 % dip for 3 ms
30 % dip for 10 ms
60 % dip for 100 ms
95 % dip for 5000 ms
10 % THD
3 % Negative Phase Sequence
Nominal 50 Hz or 60 Hz (± 4 %) A
Depth = 40 %
Area = 250 % x degrees
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
Performance
Criterion
A
A
A
A
A
A
C
C
D
A
A
A