Page 26 of 500
Placing the fourth module on a column
Figure 12
Power and system monitor connections
Top cap
Module 3
Module 2
(Modules 0 and 1 below)
553-3001-210 Standard 14.00 June 1999
2
Connect the module-to-module power and system monitor cables:
•
Connect the power connectors between the modules (see Figure 12).
•
Connect the system monitor cable from connector J2 on the third
module to J1 on the fourth module.
Note: There are no power or system monitor connectors in the NT8D36
InterGroup Module; connect the top cap cables (extra length is provided)
to the module below the InterGroup Module.
3
Reinstall the I/O safety panel in each module.
I/O safety
panel
I/O safety
panel
Rear of the column
4
Replace the module covers.
Power connectors
between modules
System monitor
connector —
J2 in Module 2 to
J1 in Module 3
553-5068
553-5068