Page 306 of 500
553-3001-210 Standard 14.00 June 1999
Performing acceptance tests
1
Verify that the green LED on each power supply is lit and that each red
column LED is OFF.
2
Set the power supply to OFF. If there is an MPDU in the module, use the
associated circuit breaker on the MPDU. If there is a switch on the power
supply, use the switch.
The green LED on the power supply should go out.
The red column LED should light.
The system terminal should display PWR0002 and BSD090.
Note: If the power supply is in an IPE Module, XMI messages may be
generated.
The system terminal should then display BSD000.
3
Set the power supply to ON.
The green LED on the power supply should light.
The red column LED should go out.
The system terminal should display PWR0000.
4
Set the power supply to OFF. Wait until the red column LED lights, then
unseat the power supply.
The red column LED should remain lit.
The system terminal should display PWR0002, BSD090, BSD000,
and PWR0003.
5
Make sure the power supply switch is OFF and then push it back into the
slot. Set the power supply to ON.
The green LED on the power supply should light.
The red column LED should go out.
The system terminal should display PWR0000.