553-3001-210 Standard 14.00 June 1999
Appendix A: NT0R72, NT6D82, QBL12, QBL15, QCA13
Turn the FLT potentiometer 1/4 turn counterclockwise.
Set the AC BRKR switch to OFF, then back to ON.
Check the voltmeter. Slowly turn the FLT potentiometer clockwise.
The voltmeter reading should increase until the desired high voltage
shutdown value is reached and then drop to 0 volts.
If necessary, repeat these adjustments until the desired level for high
voltage shutdown is set.
7
Turn the FLT potentiometer to obtain the desired float voltage reading
(see Table 102). Set the AC circuit breaker to OFF and then back ON.
8
If wires where removed from the SENS terminals on TB4, remove the
jumper straps and reconnect the black wire to +SENS and the red wire to
-SENS. Store the jumper straps under the two screws provided adjacent
to TB4.
9
Perform this procedure on each rectifier.
Table 102
Rectifier settings
Specification
High voltage shutdown
Float voltage
Range
–56.5 to –57.5 V
–51.5 to –54.0 V