42
Use of a Non-Combustible Mantel Below Listed Mantel Clearances
Each gas fireplace has a unique set of mantel requirements. If you wish to place a non-
combustible mantel at a lesser height than specified in this manual, it will need to meet the
following requirements:
The header (the framing member above the fireplace opening) must be non-combustible.
The facing must be non-combustible and extend to the header (or mantel, whichever is
greater). The facing must also span the entire width of the mantel.
See the illustration below for additional requirements.
© Travis Industries
Installation
(for qualified installers only)
4/23/2021 - 1353
4415HO GSR2