Mantel Requirements; Mantel Column Clearances - FireplaceXtrordinair ProBuilder 72 Linear Installation Manual

Table of Contents

Advertisement

Mantel Requirements

Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured from the
non-combustible facing) must fall within the shaded portion of the table.
Any material above the fireplace that protrudes more than 3/4" (19mm) from the non-combustible facing is
considered a mantel and must meet the mantel requirements.
47" (1194mm)
46" (1169mm)
45" (1143mm)
Mantel
44" (1118mm)
Height
43" (1093mm)
Above
42" (1067mm)
Base (a)
41" (1042mm)
40" (1016mm)
39" (991mm)
38" (966mm)
37" (941mm)
36" (916mm)
35" (890mm)

Mantel Column Clearances

Combustible mantel columns (legs) require a 0" (0mm) clearance to the side of the fireplace (they must
be to the side of the fireplace).
Non-combustible mantel columns do not have a minimum clearance.
© Travis Industries
Installation
(for qualified installers only)
Maximum Mantel Depth (b)
b
a
4/21/20 - 1458
PB 72 MV/GSB2/GSR2 Install
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

MvProbuilder 72 linear gsb2Probuilder 72 linear gsr2

Table of Contents