A# Duress Relay
Default:
0
0, 1 to 128 for D9412GV3, 1 to 64
Selection:
for D7412GV3, A, B, or C
Activates when a Duress alarm is generated from a
keypad assigned to the specified area.
Burg Time needs a bell period
programmed and A# Duress Enable
must be Yes. This relay activates when
the Burg Bell starts and deactivates when
the Burg Bell time ends. The Burg Bell
pattern has no effect on this relay
function.
A# Perimeter Fault
Default:
0
0, 1 to 128 for D9412GV3, 1 to 64
Selection:
for D7412GV3, A, B, or C
Activates when a Controlled Perimeter point (P##
Type 1) assigned to the specified area is faulted,
regardless of the armed state of the area. This relay
provides a steady output until all Perimeter points in
the area return to normal.
This relay does not activate on interior
faults. To detect all area point faults,
program all points as Perimeter points in
the area where this relay is assigned.
A# Silent Alarm
Default:
0
Selection:
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
This relay activates when a point assigned to the
specified area and programmed for P## Silent Bell
goes into alarm.
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Panel and Area Wide Parameters

2.12.2 Panel-Wide Relays

The following eleven relay options activate when they
occur anywhere in the control panel. They are not
restricted by area boundaries.
AC Failure
Default:
Selection:
Activates when the control panel responds to an AC
power failure as programmed in AC Fail Time in
Section 2.4 Power Supervision on page 29. This
relay automatically resets when AC power restores.
Battery Trouble
Default:
Selection:
Activates when battery voltage falls below 85% of
capacity (12.1 VDC) for a fully charged (13.8 VDC)
battery, or when the battery is in a missing condition.
This relay automatically resets when battery power
restores.
Phone Fail
Default:
Selection:
Activates when a telephone line failure occurs. A time
must be entered in Ph Supv Time (refer to Section
2.2 Phone Parameters on page 14) for this relay to
activate. This relay resets automatically when restoral
of the phone line(s) occurs.
Get other manuals https://www.bkmanuals.com
0
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Use this relay to create audible
annunciation. Enable the keypad's
trouble sounders for all applications
except commercial fire systems.
0
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C
Use this relay to create audible
annunciation. Enable the keypad's
trouble sounders for all applications
except commercial fire systems.
0
0, 1 to 128 for D9412GV3, 1 to 64
for D7412GV3, A, B, or C