Commissioning
2.2 STARTER commissioning tool
7. Select the drive unit and call the shortcut menu "Target device > Online access ...".
8. Then click on the "Module addresses" tab.
Assigning an IP address and a name to the drive unit
With the STARTER commissioning tool, you can assign an IP address and a name to the
PROFINET interface (e.g. CBE20) of the drive unit. The following steps are required:
1. Connect the programming device via a Crosslink-Ethernet cable with the CBE20, inserted
2. Switch on the Control Unit.
3. Open the STARTER commissioning tool.
78
You can then check the IP address of the integrated Ethernet interface as follows:
The IP address that you set must be located under "Connect to target station".
Figure 2-14
Setting online access
in the CU320-2.
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Commissioning Manual