Siemens SINAMICS S120 Commissioning Manual page 193

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 2- 18
Parameterization in the drive:
Parameter
Input
p0600
Motor temperature sensor for monitoring
20: Temperature sensor via BICO interconnection p0608
p0601
Motor temperature sensor, sensor type
11: Evaluation via several temperature channels BICO
p0606
Motor temperature timer
0 to 2s
Sets the timer for the alarm threshold for the motor temperature monitoring, if alarm with timer was
selected in p4610...4613.
This timer is started when the temperature alarm threshold (p0604) is exceeded.
If the timer expires before the temperature falls below the alarm threshold, then fault F07011 is
output.
p0608
[0...3] CI: Motor temperature, signal source 2
Sets the signal source 2 for the evaluation of the motor temperature via a BICO interconnection, e.g.
[0]: Motor temperature channel 1 TM120 . r4105[0]
[1]: Motor temperature channel 2 TM120 . r4105[1]
[2]: Motor temperature channel 3 TM120 . r4105[2]
[3]: Motor temperature channel 4 TM120 . r4105[3]
p4610...p4613
Motor temperature sensor 1...4 sensor type
Sets the temperature sensor type for the motor temperature monitoring. The following values are
possible for torque motors:
0: No sensor
10: PTC fault
12: PTC alarm & timer
20: KTY84
30: Bimetallic NC contact fault
32: Bimetallic NC contact alarm & timer
If you make a selection with timer, you must pre-assign parameter p0606 with the
corresponding timer of a maximum of 2 s.
Table 2- 19
Parameterization in Terminal Module TM120
Parameter
Input
p4100[0...3]
TM120 temperature evaluation, sensor type
Sets the temperature evaluation of Terminal Module TM120.
This means that the temperature sensor type is selected and the evaluation is activated. The
following values are possible:
0: Evaluation deactivated
1: PTC thermistor
2: KTY84
4: Bimetallic NC contact
Check the temperature sensors in the same way as described for Sensor Module External
SME12x. Test each individual temperature channel by withdrawing the connection.
Commissioning Manual
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
2.13 Commissioning SIMOTICS 1FW6 built-in torque motors
Commissioning
191

Advertisement

Table of Contents
loading

Table of Contents