19 message types per drive object can be changed.
Note
If BICO interconnections exist between drive objects, all interconnected objects must be
configured.
Example:
The TM31 has BICO interconnections with drive 1 and 2 and F35207 is to be reconfigured
as an alarm.
• p2118[n] = 35207 and p2119[n] = 2
• These settings are required for for TM31, drive 1 and drive 2.
Note
Only those messages which are listed in the indexed parameters can be changed as
desired. All other message settings retain their factory settings or are reset to the factory
settings.
Examples:
• In the case of messages listed via p2128[0...19], the message type can be changed. The
• The fault response of fault F12345 has been changed via p2100[n]. The factory settings
Triggering on messages (example)
Select message
p2128[0] = 1001
or
p2128[1] = 1002
Note
The value from CO: r2129 can be used as group trigger.
CO: r2129 = 0 No selected message has been output.
CO: r2129 > 0 Group trigger.
At least one selected message has been output.
The individual binector outputs BO: r2129 should be investigated.
Commissioning Manual
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
factory setting is set for all other messages.
should be restored (p2100[n] = 0).
Trigger signal
BO: r2129.0
BO: r2129.1
Diagnostics
3.5 Fault and alarm messages
303