Diagnostics
3.2 Diagnostics via STARTER
Offset
The offset is applied additively to the signal to be output. The signal to be output can thus be
displayed within the measuring range.
Limitation
● Limitation On
● Limitation off
Example of measured value output via a measuring socket
The actual speed (r0063) is to be output for a drive via measuring socket T1.
The following settings should be made:
1. Connect and set the measuring device.
2. Interconnect the signal (e.g. STARTER).
3. Parameterize the signal characteristic (scaling, offset, limitation).
288
If signals are output outside the permissible measuring range, the signal is limited to 4.98
V or to 0V.
The output of signals outside the permissible measuring range causes a signal overflow.
In the event of an overflow, the signal jumps from 0 V to 4.98 V or from 4.98 to 0 V.
Interconnect the connector input (CI) belonging to the measuring socket with the desired
connector output (CO):
CI: p0771[1] = CO: r0063
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Commissioning Manual