Canceling Stopping Delay Times - Siemens SINUMERIK 840D sl Function Manual

Safety integrated
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

Safety functions integrated in the system/drive
7.3 Safe Stops A-F
Figure 7-10
Which SGE/SGA are required for the test stop of external STOPs?
The following SGE/SGA can be used to perform the test stop for external STOPs:
NCK monitoring channel
Drive monitoring channel
7.3.10

Canceling stopping delay times

The specified transition times
SG → SBH
STOP C → SBH
STOP D → SBH
STOP E → SBH
define the time period from requesting a stop until switchover to a Safe Operating Stop. These
stopping delay times should be parameterized so that for the worst case scenario (maximum
velocity, low acceleration capability), the axis or spindle involved can stop within this time
132
Sequence of the test stop for external STOPs. Example: External STOPs A, B, C, D, E
are used
NCK-SGE "Deselect ext. STOP A
NCK-SGA "STOP A/B is active
NCK-SGE "Deselect ext. STOP C
NCK-SGA "STOP C is active
NCK-SGE "Deselect ext. STOP D
NCK-SGA "STOP D is active
NCK-SGE "Deselect ext. STOP E
NCK-SGA "STOP E is active"
PLC-SGE "Deselect ext. STOP A
PLC-SGA "STOP A/B is active"
PLC-SGE "Deselect ext. STOP C"
PLC-SGA "STOP C is active"
PLC-SGE "Deselect ext. STOP D"
PLC-SGA "STOP D is active"
PLC-SGE "Deselect ext. STOP E"
PLC-SGA "STOP E is active"
$MA_SAFE_VELO_SWITCH_DELAY
$MA_SAFE_STOP_SWITCH_TIME C
$MA_SAFE_STOP_SWITCH_TIME D
$MA_SAFE_STOP_SWITCH_TIME E
Function Manual, 12/2017, 6FC5397-4BP40-6BA1
Safety Integrated