Options
8.32 L37, DC interface incl. pre-charging input circuit for the relevant DC link capacitance
● Verify that the equipment is de-energized at the measuring points provided in the cabinet
● Check that there is no voltage on the motor connections.
● You must avoid coming into contact with the DC busbar when replacing a power block!
● When replacing components, make sure that no screws or small parts fall into the
● Remove the fan fuse and fuse for the 24 V DC power supply.
Note
Compliance with legal regulations
You must observe the applicable legal regulations when carrying out all work!
The following figures show the location of the voltage source once disconnected from the DC
busbar and the associated measuring points to verify isolation from the supply in the Cabinet
Module.
8.32.3.2

Accessibility of the DC connection to the Motor Module

Figure 8-40
490
(see figures below).
cabinet.
Front view
Cabinet Modules
Manual, 03/2013, A5E03263538A