Siemens SINAMICS S120 Manual page 469

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor cable lengths
Table 8- 42
Maximum motor cable lengths when using motor reactors for Booksize Cabinet Kits
Order no.
Power
6SL3720-
in kW
2TE13-0AB0
2 x 1.6
2TE15-0AB0
2 x 2.7
2TE21-0AB0
2 x 4.8
2TE21-8AB0
2 x 9.7
1TE13-0AB0
1.6
1TE15-0AB0
2.7
1TE21-0AB0
4.8
1TE21-8AB0
9.7
1TE23-0AB0
16
1TE24-5AB0
24
1TE26-0AB0
32
1TE28-5AB0
46
1TE31-3AB0
71
1TE32-8AB0
107
Note
Maximum motor cable length
When motor reactors are used, the maximum motor cable lengths for Motor Modules in
chassis format is 300 m (shielded) or 450 m (unshielded).
Cabinet Modules
Manual, 03/2013, A5E03263538A
Current
in A
without motor reactors
Shielded
Unshielded
2 x 3
50
2 x 5
50
2 x 9
50
2 x 18
50
3
50
5
50
9
50
18
70
30
100
45
100
60
100
85
100
132
100
200
100
8.25 L08/L09, motor reactor/2 motor reactors in series
Maximum motor cable length in m
With 1 motor reactor (L08)
Shielded
Unshielded
75
100
75
100
75
135
75
160
75
100
75
100
75
135
100
160
150
190
150
200
150
200
150
200
150
200
150
200
With 2 motor reactors
(L09)
Shielded
Unshielded
150
-
150
-
200
-
240
-
150
-
150
-
200
-
240
320
280
375
300
400
300
400
300
400
300
400
300
400
Options
-
-
-
-
-
-
-
480
560
600
600
600
600
600
467

Hide quick links:

Advertisement

Table of Contents
loading