P11, Measuring Instrument For Line Values With Profibus Connection (Installed In The Cabinet Door) - Siemens SINAMICS S120 Manual

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

8.57 P11, measuring instrument for line values with PROFIBUS connection (installed in the cabinet door)

Note
Current transformers are required in the Line Connection Module to measure line currents.
Option L41 (current transformer upstream of the main switch) is included in option P10. The
measuring instrument "DIRIS A40" is wired according to connection type 3NBL/4NBL in the
factory.
The current transformers must not be operated unloaded.
Note
Additional information
Detailed and comprehensive instructions and information regarding the "DIRIS A40"
measuring instrument can be found in the accompanying operating instructions, These
operating instructions are available as additional documentation on the customer DVD
supplied with the device.
8.57
P11, measuring instrument for line values with PROFIBUS
connection (installed in the cabinet door)
Availability of option
This option is available for the following S120 Cabinet Modules:
● Line Connection Modules
Description
A "SENTRON PAC4200" measuring instrument with display, installed in the cabinet door of
the Line Connection Module, acquires measured values of the power supply. In addition to
these measured values, additional plant values (such as power and power factor, etc.) are
calculated from the measured values using powerful, state-of-the art microprocessors. The
measuring instrument has a PROFIBUS interface that enables a transfer rate of up to
12 Mbit/s.
The device can measure the following as standard:
● Actual currents per phase and actual currents of the neutral conductor.
● Average currents and maximum currents over programmable time intervals from 1 to
● Phase-to-neutral voltages and phase-to-phase voltages
● Frequency (Hz)
● Four-quadrant measurement of the actual, average, and maximum active power (+/-),
● Display of active energy in kWh.
● Power factor (PF) per phase and in total with the specifications "L" for inductive and "C"
Cabinet Modules
Manual, 03/2013, A5E03263538A
60 min.
reactive power (+/-) and apparent power (+/-) per phase and in total over programmable
time intervals from 1 to 60 min.
for capacitive.
Options
545

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents