Configuring the "Overtemperature" checkback

The checkback contact of the braking resistor thermostatic switch must be wired to a digital
input so that the drive is shut down in the event of a malfunction.
● Assumption 1:
● Assumption 2:
● Setting required:
Control engineering measures must also be implemented to prevent the drive from starting
up again before the braking resistor has had a chance to cool down properly.
Cabinet Modules
Manual, 03/2013, A5E03263538A
Terminal strip X10 thermostatic switch checkback contact
Function
Thermostatic switch checkback contact
Normally-closed contact, 250 V AC, max. 1 A
The thermostatic switch feedback signal contact is wired to digital input 3 (DI3) of CU320-
2 (-X122:4)
Once the thermostatic switch trips, "External Fault 3" (F7862) is triggered and the drive is
shut down with OFF2.
(Drive) p2108 = (CU320-2) 0722.3