Electrical installation
4.6 Connections
Table 4- 5
X101, terminal block for routing the auxiliary voltage connecting cables
Terminal
1
2
3
4
5
6
The maximum load capability of the auxiliary power supply system is 80 A.
Max. connectable cross-section: 35 mm
Tightening torque: 2 Nm
Auxiliary power module in the Line Connection Module
The auxiliary power module in the Line Connection Module consists of the -X100 terminal
block for feeding in and routing the auxiliary voltages in both directions. No voltage taps are
available to the customer.
Figure 4-8
84
Designation
Assigned voltages
L1
Line voltage (for fan supply via transformer):
L2
380 to 480 V 2 AC or
500 to 690 V 2 AC (max. 759 V AC)
L1
230 V 1 AC (max. 265 V AC)
N
P24
24 V DC for the electronics power supply (max. 30
V DC)
M
2
Auxiliary power module in the Line Connection Module
Rated current
Max. 80 A
Max. 80 A
Max. 80 A
Cabinet Modules
Manual, 03/2013, A5E03263538A