Siemens SIMOTICS L-1FN3 Configuration Manual page 573

Linear motors peak and continuous load motors
Hide thumbs Also See for SIMOTICS L-1FN3:
Table of Contents

Advertisement

Note
Requirements of coupled motors
• Check the phase angles of the EMFs
• Ensure that there is a sufficiently rigid mechanical coupling.
• Position the motors as close together as possible.
• The electrical parallel connection is not suitable for gantry applications.
If you connect linear motors in parallel on a shared secondary section track, the primary
sections must be positioned with a defined distance between them.
This produces matching phase angles of the EMFs. For separate secondary section tracks,
you must also consider the position of the tracks relative to each other.
Check whether the phase angles of the EMFs differ by no more than ±10° (see SINAMICS
S120 Commissioning Manual).
1FN3 linear motors
Configuration Manual, 10/2018, 6SN1197-0AB86-0BP2
Tandem arrangement: Master and stoker with the same cable outlet direction on the same
secondary section track
Janus arrangement: Master and stoker with opposite cable outlet directions on the same sec-
ondary section track
Parallel arrangement: Master and stoker with the same cable outlet direction on a separate
secondary section track
Anti-parallel arrangement: Master and stoker with opposite cable outlet directions on a sepa-
rate secondary section track
Coupled motors
10.2 Master and stoker
571

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents