Siemens SIMOTICS L-1FN3 Configuration Manual page 130

Linear motors peak and continuous load motors
Hide thumbs Also See for SIMOTICS L-1FN3:
Table of Contents

Advertisement

Configuration
5.3 Examples
Peak load motor
1FN3150-4WC00-0BA1
Continuous load motor
1FN3150-4NB80-0BA1
Final selection of the primary section
For the example considered here, for a peak load motor, primary section 1FN3150-4WC00-
0BA1 is suitable, and for a continuous load motors, primary section 1FN3150-4NB80-0BA1.
Which primary section is best suited to the specified duty cycle can be derived from the
following summary:
Motor
Peak load motor
Continuous load motor 1FN3150-4NB80-0BA1
Decision-making criteria for the primary section include:
● Size and installation conditions
● Thermal conditions
● Idle times
● Power reserves for peak and continuous loads
● Acceleration and velocity class
● Velocity class
● Converter power module
128
Article No.
1FN3150-4WC00-0BA1
F
= m
· a + F
= 2617 N
1
ges
r
F
= F
= 100 N
2
r
F
= -m
· a + F
= - 2417 N
3
ges
r
F
= 0 N
4
F
= -m
· a - F
= - 2617 N
5
ges
r
F
= F
- F
= - 100 N
6
4
r
F
= m
· a - F
= 2417 N
7
ges
r
⇒ F
= 1246 N
eff
The effective force therefore remains
below the permissible value of F
1350 N
F
= m
· a + F
= 2777 N
1
ges
r
F
= F
= 100 N
2
r
F
= -m
· a + F
= - 2577 N
3
ges
r
F
= 0 N
4
F
= -m
· a - F
= - 2777 N
5
ges
r
F
= F
- F
= - 100 N
6
4
r
F
= m
· a - F
= 2577 N
7
ges
r
⇒ F
= 1325 N
eff
The effective force therefore remains
below the permissible value of F
=1810 N
Values from the data sheet
F
MAX
3300 N
1350 N
3060 N
1810 N
Configuration Manual, 10/2018, 6SN1197-0AB86-0BP2
Travel to position s
Dwell time
Travel to position s
=
N
Travel to position s
Dwell time
Travel to position s
N
Values from the duty cycle
F
F
N
L,MAX
2617 N
2773 N
MAX
0
MAX
0
F
eff
1246 N
1325 N
1FN3 linear motors