Selecting The Module Versions; Module Versions At Configuration With Step 7 - Siemens Simatic ET 200SP Manual

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Configuration / address space

4.2 Selecting the module versions

4.2
Selecting the module versions
Introduction
The AI Energy Meter HF has different module versions.
During the configuration you use the selection of the module version to specify which
measured values can be read.
Each module version supplies quality information via the input user data.
With the exception of the module version "2 I / 2 Q" you can read the measured values as
user data cyclically from the process image. At each module version you have the option to
read measured value records from the AI Energy Meter HF by using the RDREC instruction
asynchronously.
Influence of the module version on the address space
Note
Influence of the AI Energy Meter HF on the maximum configuration of the ET 200SP
The available address space of the ET 200SP is influenced by the following factors:
• CPU or interface module
• Plugged I/O modules
The address space made additionally available by the AI Energy Meter HF is essentially
influenced by the length of the user data supplied. The module version determines the length
of the user data, which can be supplied by the AI Energy Meter HF at maximum.
4.2.1

Module versions at configuration with STEP 7

Module versions with fixed user data assignment
Module version
User data
2 I / 2 Q
No cyclic user data.
Access to measured values
through "Read data record".
EE@Industry E0
User data in accordance
with EE@Industry meas-
urement data profiles
EE@Industry E1
EE@Industry E2
EE@Industry E3
32
Address space
Comment
2-byte inputs
Information about the structure of the 2 I / 2 Q
2-byte outputs
module version is available in the appendix Mod-
ule version "2 I / 2 Q" (Page 192).
12-byte inputs /
Information about the structure of the
20-byte outputs
EE@Industry measured data profiles is available
in the appendix Module version "EE@Industry
4-byte inputs /
measurement data profile E0 / E1 / E2 / E3"
20-byte outputs
(Page 203).
12-byte inputs /
20-byte outputs
104-byte inputs /
20-byte outputs
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA