  • Page 2 ___________________ Preface ___________________ Guide to the documentation ___________________ SIMATIC Product overview ___________________ BaseUnits for I/O modules ET 200SP BaseUnits ___________________ BaseUnits for motor starters (6ES7193-6BP.../3RK1908-0AP00…) Dimension drawings of I/O ___________________ modules Manual Dimension drawings of motor ___________________ starters 12/2016 A5E03727049-AG...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
  • Page 5: Table Of Contents

    Table of contents Preface ..............................4 Guide to the documentation ........................8 Product overview ..........................11 BaseUnits for I/O modules ........................15 BU15-P16+A10+2D (BU type A0) ..................15 3.1.1 Product overview ........................15 3.1.2 Connecting up ......................... 17 3.1.3 Technical specifications ......................18 BU15-P16+A0+2D (BU type A0) ....................
  • Page 6 Table of contents 3.10 BU20-P12+A0+4B (BU type B1) .................... 49 3.10.1 Product overview........................49 3.10.2 Connecting up ........................50 3.10.3 Technical specifications ......................51 3.11 BU20-P6+A2+4D (BU type C0) ..................... 52 3.11.1 Product overview........................52 3.11.2 Connecting ..........................54 3.11.3 Technical specifications ......................
  • Page 7: Baseunits (6Es7193-6Bp.../3Rk1908-0Ap00 Manual, 12/2016, A5E03727049-Ag

    Table of contents Dimension drawings of I/O modules ...................... 94 Dimension drawings of motor starters ....................98 BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 8: Guide To The Documentation

    Guide to the documentation The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP.
  • Page 9 Guide to the documentation Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942). "mySupport" With "mySupport", your personal workspace, you make the most of your Industry Online Support.
  • Page 10 With the TIA Selection Tool, you can generate a complete order list from your product selection or product configuration. You can find the TIA Selection Tool on the Internet (http://w3.siemens.com/mcms/topics/en/simatic/tia-selection-tool). BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 11: Product Overview

    Product overview General properties of the BaseUnits In the ET 200SP distributed I/O system, there are a number of different BaseUnits. The BaseUnit determines, among other things, the process connection, the suitable I/O modules/motor starters, and the infeed of the supply voltage. All properties can be identified by the short designation of the BaseUnit which is explained below.
  • Page 12 Product overview Properties of the BaseUnits for motor starters The following table lists the properties of the individual BaseUnits for motor starters: BaseUnit Properties BU30-MS1 Push-in terminals for opening a new potential group (24 V DC). • Feeding in of supply voltage up to a maximum supply current of 7 A DC. •...
  • Page 13 Proper use of hardware products This equipment is only allowed to be used for the applications described in the catalog and in the technical description, and only in conjunction with non-Siemens equipment and components recommended by Siemens. Correct transport, storage, installation and assembly, as well as careful operation and maintenance, are required to ensure that the product operates safely and without faults.
  • Page 14 By subscribing to the appropriate newsletter, you will ensure that you are always up-to-date and able to make changes to your system, when necessary: Siemens Newsletter (http://www.industry.siemens.com/newsletter) Sign on to the following newsletter under "Products & Solutions": • Control Components and System Engineering News •...
  • Page 15: Baseunits For I/O Modules

    BaseUnits for I/O modules BU15-P16+A10+2D (BU type A0) 3.1.1 Product overview Article number 6ES7193-6BP20-0DA0 View Figure 3-1 BaseUnit BU15-P16+A10+2D BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 16 BaseUnits for I/O modules 3.1 BU15-P16+A10+2D (BU type A0) Properties ● BaseUnit suitable for all I/O modules of the BaseUnit type "A0/A1". Can be recognized by the last two digits of the article number. – Supply voltage (L+ terminal, ground): Max. 24 VDC/10 A –...
  • Page 17: Connecting Up

    Descriptions 1 to 16 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). 1A, 2A, 3A, 4A, 5A, 6A, 7A, 8A, 9A, Protective-conductor terminal or potential bus freely usable up to 24 V DC with 10A, AUX max.
  • Page 18: Technical Specifications

    BaseUnits for I/O modules 3.1 BU15-P16+A10+2D (BU type A0) 3.1.3 Technical specifications Technical specifications of the BaseUnit BU15-P16+A10+2D 6ES7193-6BP20-0DA0 Product type designation BU15-P16+A10+2D Supply voltage Rated value (DC) 24 V External fuse for power supply lines Yes: 24 VDC / 10 A miniature circuit breaker with type B or C tripping characteristic Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 19: Bu15-P16+A0+2D (Bu Type A0)

    BaseUnits for I/O modules 3.2 BU15-P16+A0+2D (BU type A0) BU15-P16+A0+2D (BU type A0) 3.2.1 Product overview Article number 6ES7193-6BP00-0DA0 View Figure 3-3 BaseUnit BU15-P16+A0+2D BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 20 BaseUnits for I/O modules 3.2 BU15-P16+A0+2D (BU type A0) Properties ● BaseUnit suitable for all I/O modules of the BaseUnit type "A0/A1". Can be recognized by the last two digits of the article number. – Supply voltage (L+ terminal, ground): Max. 24 VDC/10 A –...
  • Page 21: Connection

    Terminal Descriptions 1 to 16 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). (AUX) No access to the AUX busbar via terminals L+, P1 / M, P2 L+: Rated supply voltage 24 V DC with max. 10 A...
  • Page 22: Technical Specifications

    BaseUnits for I/O modules 3.2 BU15-P16+A0+2D (BU type A0) 3.2.3 Technical specifications Technical specifications of the BaseUnit BU15-P16+A0+2D 6ES7193-6BP00-0DA0 Product type designation BU15-P16+A0+2D Supply voltage Rated value (DC) 24 V External fuse for power supply lines Yes: 24 VDC / 10 A miniature circuit breaker with type B or C tripping characteristic Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 23: Bu15-P16+A10+2B (Bu Type A0)

    BaseUnits for I/O modules 3.3 BU15-P16+A10+2B (BU type A0) BU15-P16+A10+2B (BU type A0) 3.3.1 Product overview Article number 6ES7193-6BP20-0BA0 View Figure 3-5 BaseUnit BU15-P16+A10+2B BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 24 BaseUnits for I/O modules 3.3 BU15-P16+A10+2B (BU type A0) Properties ● BaseUnit suitable for all I/O modules of the BaseUnit type "A0/A1". Can be recognized by the last two digits of the article number. – Current-carrying capacity per process terminal (terminal 1 to 16): Max. 2 A ●...
  • Page 25: Connection

    Descriptions 1 to 16 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). 1A, 2A, 3A, 4A, 5A, 6A, 7A, 8A, 9A, Protective conductor connection or voltage bus freely usable up to 24 V DC with 10A, AUX max.
  • Page 26: Technical Specifications

    BaseUnits for I/O modules 3.3 BU15-P16+A10+2B (BU type A0) 3.3.3 Technical specifications Technical specifications of the BaseUnit BU15-P16+A10+2B 6ES7193-6BP20-0BA0 Product type designation BU15-P16+A10+2B Supply voltage Rated value (DC) 24 V External fuse for power supply lines Yes: 24 VDC / 10 A miniature circuit breaker with type B or C tripping characteristic Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 27: Bu15-P16+A0+2B (Bu Type A0)

    BaseUnits for I/O modules 3.4 BU15-P16+A0+2B (BU type A0) BU15-P16+A0+2B (BU type A0) 3.4.1 Product overview Article number 6ES7193-6BP00-0BA0 View Figure 3-7 BaseUnit BU15-P16+A0+2B Properties ● BaseUnit suitable for all I/O modules of the BaseUnit type "A0/A1". Can be recognized by the last two digits of the article number.
  • Page 28: Connection

    Terminal Descriptions 1 to 16 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). (AUX) No access to the AUX busbar via terminals L+, P1 / M, P2 L+: Rated supply voltage 24 V DC with max. 10 A...
  • Page 29: Technical Specifications

    BaseUnits for I/O modules 3.4 BU15-P16+A0+2B (BU type A0) 3.4.3 Technical specifications Technical specifications of the BaseUnit BU15-P16+A0+2B 6ES7193-6BP00-0BA0 Product type designation BU15-P16+A0+2B Supply voltage Rated value (DC) 24 V External fuse for power supply lines Yes: 24 VDC / 10 A miniature circuit breaker with type B or C tripping characteristic Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 30: Bu15-P16+A0+12D/T (Bu Type A1)

    BaseUnits for I/O modules 3.5 BU15-P16+A0+12D/T (BU type A1) BU15-P16+A0+12D/T (BU type A1) 3.5.1 Product overview Order number 6ES7193-6BP40-0DA1 View Figure 3-9 BaseUnit BU15-P16+A0+12D/T BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 31 BaseUnits for I/O modules 3.5 BU15-P16+A0+12D/T (BU type A1) Properties ● BaseUnit for all I/O modules of BaseUnit type "A1". Can be recognized by the last two digits of the order number. Note Using another I/O module can trigger an internal, non-exchangeable fuse and you must exchange the terminal box.
  • Page 32: Connection

    1 to 16 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). 1B, 2B, 3B, 4B, 5B / 2 x 5 add-on terminals for the infeed of a supply voltage up to 24 V DC with max. 10 A...
  • Page 33: Technical Specifications

    BaseUnits for I/O modules 3.5 BU15-P16+A0+12D/T (BU type A1) 3.5.3 Technical specifications Technical specifications of the BaseUnit BU15-P16+A0+12D/T 6ES7193-6BP40-0DA1 Product type designation BU15-P16+A0+12D/T Supply voltage Rated value (DC) 24 V External fuse for power supply lines Yes: 24 VDC / 10 A miniature circuit breaker with type B or C tripping characteristic Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 34: Bu15-P16+A0+2D/T (Bu Type A1)

    BaseUnits for I/O modules 3.6 BU15-P16+A0+2D/T (BU type A1) BU15-P16+A0+2D/T (BU type A1) 3.6.1 Product overview Article number 6ES7193-6BP00-0DA1 View Figure 3-11 BaseUnit BU15-P16+A0+2D/T BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 35 BaseUnits for I/O modules 3.6 BU15-P16+A0+2D/T (BU type A1) Properties ● BaseUnit for all I/O modules of BaseUnit type "A1". Can be recognized by the last two digits of the article number. Note Using another I/O module can trigger an internal, non-exchangeable fuse and you must exchange the terminal box.
  • Page 36: Connection

    Terminal Descriptions 1 to 16 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). (AUX) No access to the AUX busbar via terminals L+, P1 / M, P2 L+: Rated supply voltage 24 V DC with max. 10 A...
  • Page 37: Technical Specifications

    BaseUnits for I/O modules 3.6 BU15-P16+A0+2D/T (BU type A1) 3.6.3 Technical specifications Technical specifications of the BaseUnit BU15-P16+A0+2D/T 6ES7193-6BP00-0DA1 Product type designation BU15-P16+A0+2D/T Supply voltage Rated value (DC) 24 V External fuse for power supply lines Yes: 24 VDC / 10 A miniature circuit breaker with type B or C tripping characteristic Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 38: Bu15-P16+A0+12B/T (Bu Type A1)

    BaseUnits for I/O modules 3.7 BU15-P16+A0+12B/T (BU type A1) BU15-P16+A0+12B/T (BU type A1) 3.7.1 Product overview Article number 6ES7193-6BP40-0BA1 View Figure 3-13 BaseUnit BU15-P16+A0+12B/T BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 39 BaseUnits for I/O modules 3.7 BU15-P16+A0+12B/T (BU type A1) Properties ● BaseUnit suitable for all I/O modules of BaseUnit type "A1". Can be recognized by the last two digits of the article number. Note Using another I/O module can trigger an internal, non-exchangeable fuse and you must exchange the terminal box.
  • Page 40: Connection

    1 to 16 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). 1B, 2B, 3B, 4B, 5B / 2 x 5 add-on terminals for the infeed of a supply voltage up to 24 V DC with max. 10 A...
  • Page 41: Technical Specifications

    BaseUnits for I/O modules 3.7 BU15-P16+A0+12B/T (BU type A1) 3.7.3 Technical specifications Technical specifications of the BaseUnit BU15-P16+A0+12B/T 6ES7193-6BP40-0BA1 Product type designation BU15-P16+A0+12B/T Supply voltage Rated value (DC) 24 V External fuse for power supply lines Yes: 24 VDC / 10 A miniature circuit breaker with type B or C tripping characteristic Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 42: Bu15-P16+A0+2B/T (Bu Type A1)

    BaseUnits for I/O modules 3.8 BU15-P16+A0+2B/T (BU type A1) BU15-P16+A0+2B/T (BU type A1) 3.8.1 Product overview Article number 6ES7193-6BP00-0BA1 View Figure 3-15 BaseUnit BU15-P16+A0+2B/T BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 43 BaseUnits for I/O modules 3.8 BU15-P16+A0+2B/T (BU type A1) Properties ● BaseUnit suitable for all I/O modules of BaseUnit type "A1". Can be recognized by the last two digits of the article number. Note Using another I/O module can trigger an internal, non-exchangeable fuse and you must exchange the terminal box.
  • Page 44: Connection

    Terminal Descriptions 1 to 16 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). (AUX) No access to the AUX busbar via terminals L+, P1 / M, P2 L+: Rated supply voltage 24 V DC with max. 10 A...
  • Page 45: Technical Specifications

    BaseUnits for I/O modules 3.8 BU15-P16+A0+2B/T (BU type A1) 3.8.3 Technical specifications Technical specifications of the BaseUnit BU15-P16+A0+2B/T 6ES7193-6BP00-0BA1 Product type designation BU15-P16+A0+2B/T Supply voltage Rated value (DC) 24 V External fuse for power supply lines Yes: 24 VDC / 10 A miniature circuit breaker with type B or C tripping characteristic Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 46: Bu20-P12+A4+0B (Bu Type B0)

    BaseUnits for I/O modules 3.9 BU20-P12+A4+0B (BU type B0) BU20-P12+A4+0B (BU type B0) 3.9.1 Product overview Article number 6ES7193-6BP20-0BB0 View Figure 3-17 BaseUnit BU20-P12+A4+0B Properties ● BaseUnit suitable for all I/O modules of the BaseUnit type "B0/B1". Can be recognized by the last two digits of the article number.
  • Page 47: Connecting

    1 to 12 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). 1A, 2A, 3A, 4A, AUX Protective conductor connection or voltage bus (freely usable up to 230 V AC/ DC with max 10 A). If you connect a voltage, it must belong to the same potential group as the rated supply voltage.
  • Page 48: Technical Specifications

    BaseUnits for I/O modules 3.9 BU20-P12+A4+0B (BU type B0) 3.9.3 Technical specifications Technical specifications of the BaseUnit BU20-P12+A4+0B 6ES7193-6BP20-0BB0 Product type designation BU20-P12+A4+0B Supply voltage Rated value (DC) 24 V Rated value (AC) 230 V; 110 V Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 49: Bu20-P12+A0+4B (Bu Type B1)

    BaseUnits for I/O modules 3.10 BU20-P12+A0+4B (BU type B1) 3.10 BU20-P12+A0+4B (BU type B1) 3.10.1 Product overview Article number 6ES7193-6BP20-0BB1 View Figure 3-19 BaseUnit BU20-P12+A0+4B Properties ● BaseUnit suitable for all I/O modules of the BaseUnit type "B1". Can be recognized by the last two digits of the article number.
  • Page 50: Connecting Up

    BaseUnits for I/O modules 3.10 BU20-P12+A0+4B (BU type B1) 3.10.2 Connecting up Pin assignment Table 3- 10 Pin assignment for BaseUnit BU20-P12+A0+4B Pin assignment for BaseUnit BU20-P12+A0+4B Terminal Descriptions 1 to 12 Assignment is determined by the I/O module. See manual I/O Module (AUX) No access to the AUX busbar via terminals 1L, 2L, (P1) / 1N, 2N, (P2)
  • Page 51: Technical Specifications

    BaseUnits for I/O modules 3.10 BU20-P12+A0+4B (BU type B1) 3.10.3 Technical specifications Technical specifications of the BaseUnit BU20-P12+A0+4B 6ES7193-6BP20-0BB1 Product type designation BU20-P12+A0+4B Supply voltage Rated value (DC) 24 V Rated value (AC) 230 V; 110 V Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 52: Bu20-P6+A2+4D (Bu Type C0)

    BaseUnits for I/O modules 3.11 BU20-P6+A2+4D (BU type C0) 3.11 BU20-P6+A2+4D (BU type C0) 3.11.1 Product overview Article number 6ES7193-6BP20-0DC0 View Figure 3-21 BaseUnit BU20-P6+A2+4D BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 53 BaseUnits for I/O modules 3.11 BU20-P6+A2+4D (BU type C0) Properties ● BaseUnit suitable for all I/O modules of BaseUnit type "C0/C1". Can be recognized by the last two digits of the article number. – Supply voltage (terminal 1L, 2L / 1N, 2N): Max. 230 V AC/10 A –...
  • Page 54: Connecting

    1 to 6 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). 1A, 2A, AUX Protective conductor connection or voltage bus freely usable up to 230 V AC/ DC with max 10 A. If you connect a voltage, it must belong to the same potential group as the rated supply voltage.
  • Page 55: Technical Specifications

    BaseUnits for I/O modules 3.11 BU20-P6+A2+4D (BU type C0) 3.11.3 Technical specifications Technical specifications of the BaseUnit BU20-P6+A2+4D 6ES7193-6BP20-0DC0 Product type designation BU20-P6+A2+4D Supply voltage Rated value (DC) 24 V; 30 V Rated value (AC) 230 V; 110 V External fuse for power supply lines Yes;...
  • Page 56: Bu20-P6+A2+4B (Bu Type C1)

    BaseUnits for I/O modules 3.12 BU20-P6+A2+4B (BU type C1) 3.12 BU20-P6+A2+4B (BU type C1) 3.12.1 Product overview Article number 6ES7193-6BP20-0BC1 View Figure 3-23 BaseUnit BU20-P6+A2+4B BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 57 BaseUnits for I/O modules 3.12 BU20-P6+A2+4B (BU type C1) Properties ● BaseUnit suitable for all I/O modules of BaseUnit type "C0/C1". Can be recognized by the last two digits of the article number. – Current-carrying capacity per process terminal (terminal 1 to 4): Max. 5 A –...
  • Page 58: Connecting

    1 to 6 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300). 1A, 2A, AUX Protective conductor connection or voltage bus freely usable up to 230 V AC/ DC with max 10 A. If you connect a voltage, it must belong to the same potential group as the rated supply voltage.
  • Page 59: Technical Specifications

    BaseUnits for I/O modules 3.12 BU20-P6+A2+4B (BU type C1) 3.12.3 Technical specifications Technical specifications of the BaseUnit BU20-P6+A2+4B 6ES7193-6BP20-0BC1 Product type designation BU20-P6+A2+4B Supply voltage Rated value (DC) 24 V; 30 V Rated value (AC) 230 V; 110 V Current carrying capacity Current carrying capacity up to 60 °C, max.
  • Page 60: Bu20-P12+A0+0B (Bu Type D0)

    BaseUnits for I/O modules 3.13 BU20-P12+A0+0B (BU type D0) 3.13 BU20-P12+A0+0B (BU type D0) 3.13.1 Product overview Article number 6ES7193-6BP00-0BD0 View Figure 3-25 BaseUnit BU20-P12+A0+0B BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 61 BaseUnits for I/O modules 3.13 BU20-P12+A0+0B (BU type D0) Properties ● BaseUnit suitable for all I/O modules of the BaseUnit type "D0". Can be recognized by the last two digits of the article number. – Current-carrying capacity per process terminal (terminal 1 to 12): Max. 5 A ●...
  • Page 62: Connecting

    Pin assignment for BaseUnit BU20-P12+A0+0B Pin assignment for BaseUnit BU20-P12+A0+0B Terminal Descriptions 1 to 12 Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300) Block diagram ① Backplane bus ② I/O module ③ Terminals with connection to the I/O module ④...
  • Page 63: Technical Specifications

    BaseUnits for I/O modules 3.13 BU20-P12+A0+0B (BU type D0) 3.13.3 Technical specifications Technical specifications of the BaseUnit BU20-P12+A0+0B 6ES7193-6BP00-0BD0 Product type designation BU20-P12+A0+0B Supply voltage Rated value (AC) 400 V; 230 VAC (L1/ N) Current carrying capacity Current carrying capacity up to 60 °C, max. Electrical isolation between backplane bus and supply voltage Isolation...
  • Page 64: Bu20-P8+A4+0B (Bu Type F0)

    BaseUnits for I/O modules 3.14 BU20-P8+A4+0B (BU type F0) 3.14 BU20-P8+A4+0B (BU type F0) 3.14.1 Product overview Note when you use the AUX terminals as a PE busbar: NOTICE If AUX is used as PE, AUX must be identified as green-yellow (e.g., gn/ye color-coded labels).
  • Page 65 BaseUnits for I/O modules 3.14 BU20-P8+A4+0B (BU type F0) Properties ● BaseUnit suitable for all I/O modules of the BaseUnit type "F0". Can be recognized by the last two digits of the order number. – Current carrying capacity per process terminal (terminals 1 to 4 and 9 to 12): Max. 5 A ●...
  • Page 66: Connecting Up

    1 to 4 Up to 230 VAC/VDC (AC only one phase) Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300) 9 to 12 Safe extra low voltage SELV/PELV Assignment is determined by the I/O module. See manual I/O Module (http://support.automation.siemens.com/WW/view/en/55679691/133300)
  • Page 67: Technical Specifications

    BaseUnits for I/O modules 3.14 BU20-P8+A4+0B (BU type F0) 3.14.3 Technical specifications Technical specifications of the BaseUnit BU20-P8+A4+0B 6ES7193-6BP20-0BF0 Product type designation BU20-P8+A4+0B Supply voltage Rated value (DC) See manual Rated value (AC) See manual Current carrying capacity Current carrying capacity up to 60 °C, max. 10 A Electrical isolation between backplane bus and supply voltage...
  • Page 68: Baseunits For Motor Starters

    The AUX1 bus is not supported in the BaseUnits of the SIMATIC ET 200SP motor starters. You can find assembly rules of the BaseUnits for the SIMATIC ET 200SP motor starter in the System Manual SIMATIC ET 200SP motor starters.
  • Page 69: Bu30-Ms1 - Baseunit With 24 V Dc And 500 V Ac Infeed

    BaseUnits for motor starters 4.2 BU30-MS1 - BaseUnit with 24 V DC and 500 V AC infeed BU30-MS1 - BaseUnit with 24 V DC and 500 V AC infeed 4.2.1 Product overview Article number 3RK1908-0AP00-0AP0 View Figure 4-1 BaseUnit with 24 V DC and 500 V AC infeed BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 70 1. Total current requirement of all motor starters operated on this infeed group. 2. Ambient temperature and installation type in which the motor starters are operated. You can find further information in the derating table in the Manual SIMATIC ET 200SP motor starters (https://support.industry.siemens.com/cs/ww/en/view/109479973).
  • Page 71: Connection

    L1(L), L2(N), L3, PE Power supply Assignment is determined by the motor starter. See Manual ET 200SP motor starters (https://support.industry.siemens.com/cs/ww/en/view/109479973). T1, T2, T3, PE Motor feeder 24 V DC, M 24 V DC: Supply voltage 24 V DC with max. 7 A M: Ground BaseUnits (6ES7193-6BP.../3RK1908-0AP00…)
  • Page 72 BaseUnits for motor starters 4.2 BU30-MS1 - BaseUnit with 24 V DC and 500 V AC infeed Block diagram The figure below shows the block diagram of the BaseUnit with 24 V DC and 500 V AC infeed. ① Backplane bus ②...
  • Page 73: Technical Specifications

    BaseUnits for motor starters 4.2 BU30-MS1 - BaseUnit with 24 V DC and 500 V AC infeed 4.2.3 Technical specifications Technical specifications of the BaseUnit with 24 V DC and 500 V AC infeed 3RK1908-0AP00-0AP0 Product type designation BU30-MS1 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with...
  • Page 74: Bu30-Ms2 - Baseunit With 500 V Ac Infeed

    BaseUnits for motor starters 4.3 BU30-MS2 - BaseUnit with 500 V AC infeed BU30-MS2 - BaseUnit with 500 V AC infeed 4.3.1 Product overview Article number 3RK1908-0AP00-0CP0 View Figure 4-3 BaseUnit with 500 V AC infeed BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 75: Connection

    1. Total current requirement of all motor starters operated on this infeed group. 2. Ambient temperature and installation type in which the motor starters are operated. You can find further information in the derating table in the Manual SIMATIC ET 200SP motor starters.
  • Page 76 BaseUnits for motor starters 4.3 BU30-MS2 - BaseUnit with 500 V AC infeed Block diagram The figure below shows the block diagram of the BaseUnit with 500 V AC infeed. ① Backplane bus ② Motor starter module ③ Connected power buses 24 V DC, M ④...
  • Page 77: Technical Specifications

    BaseUnits for motor starters 4.3 BU30-MS2 - BaseUnit with 500 V AC infeed 4.3.3 Technical specifications Technical specifications of the BaseUnit with 500 V AC infeed 3RK1908-0AP00-0CP0 Product type designation BU30-MS2 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC...
  • Page 78: Bu30-Ms3 - Baseunit With 24 V Dc Infeed

    BaseUnits for motor starters 4.4 BU30-MS3 - BaseUnit with 24 V DC infeed BU30-MS3 - BaseUnit with 24 V DC infeed 4.4.1 Product overview Article number 3RK1908-0AP00-0BP0 View Figure 4-5 BaseUnit with 24 V DC infeed BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 79 4.4 BU30-MS3 - BaseUnit with 24 V DC infeed Properties ● BaseUnit suitable for all fail-safe and non-fail-safe SIMATIC ET 200SP High Feature motor starters ● The BaseUnit opens a new potential group (24 V DC). The power buses P1 and P2 are interrupted to the left-hand neighboring module (BaseUnit, interface module/CPU).
  • Page 80: Connection

    BaseUnits for motor starters 4.4 BU30-MS3 - BaseUnit with 24 V DC infeed 4.4.2 Connection Pin assignment Table 4- 3 Pin assignment for BaseUnit with 24 V DC infeed Pin assignment for BaseUnit with 24 V DC infeed Terminal Descriptions T1, T2, T3, PE Motor feeder 24 V DC, M...
  • Page 81: Technical Specifications

    BaseUnits for motor starters 4.4 BU30-MS3 - BaseUnit with 24 V DC infeed 4.4.3 Technical specifications Technical specifications of the BaseUnit with 24 V DC infeed 3RK1908-0AP00-0BP0 Product type designation BU30-MS3 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC...
  • Page 82: Bu30-Ms4 - Baseunit Without Infeed

    Figure 4-7 BaseUnit without infeed Properties ● BaseUnit suitable for all fail-safe and non-fail-safe SIMATIC ET 200SP High Feature motor starters ● No new potential groups are opened with this BaseUnit. ● The potential group (24 V DC) is looped through.
  • Page 83: Connection

    BaseUnits for motor starters 4.5 BU30-MS4 - BaseUnit without infeed 4.5.2 Connection Pin assignment Table 4- 4 Pin assignment for BaseUnit without infeed Pin assignment for BaseUnit without infeed Terminal Descriptions T1, T2, T3, PE Motor feeder Block diagram The figure below shows the block diagram of the BaseUnit without infeed. ①...
  • Page 84: Technical Specifications

    BaseUnits for motor starters 4.5 BU30-MS4 - BaseUnit without infeed 4.5.3 Technical specifications Technical specifications of BaseUnit without infeed 3RK1908-0AP00-0DP0 Product type designation BU30-MS4 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC Rated operating voltage 24 V DC Max.
  • Page 85: Bu30-Ms5 Baseunit With 500 V Ac Infeed And F-Di

    BaseUnits for motor starters 4.6 BU30-MS5 BaseUnit with 500 V AC infeed and F-DI BU30-MS5 BaseUnit with 500 V AC infeed and F-DI 4.6.1 Product overview Article number 3RK1908-0AP00-0EP0 View Figure 4-9 BaseUnit with 500 V AC and F-DI BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 86 4.6 BU30-MS5 BaseUnit with 500 V AC infeed and F-DI Properties ● BaseUnit suitable for all fail-safe SIMATIC ET 200SP High Feature motor starters ● The BaseUnit handles the potential group (P1, P2) of the left-hand neighboring module. ● The BaseUnit opens a new 500 V AC infeed group. The potential group (24 V DC) is looped through.
  • Page 87: Connection

    Motor feeder F-DI, M F-DI: Connection of fail-safe signal M: Reference potential of fail-safe signal L1(L), L2(N), L3, PE Power supply Assignment is determined by the motor starter. See Manual ET 200SP motor starters (https://support.industry.siemens.com/cs/ww/en/view/109479973). BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 88 BaseUnits for motor starters 4.6 BU30-MS5 BaseUnit with 500 V AC infeed and F-DI Block diagram The figure below shows the two-phase connection with 500 V AC infeed and F-DI: ① Backplane bus ② Motor starter module ③ Connected power buses 24 V DC, M ④...
  • Page 89: Technical Specifications

    BaseUnits for motor starters 4.6 BU30-MS5 BaseUnit with 500 V AC infeed and F-DI 4.6.3 Technical specifications Technical specifications of the BaseUnit with 500 V AC infeed and F-DI 3RK1908-0AP00-0EP0 Product type designation BU30-MS5 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC...
  • Page 90: Bu30-Ms6 Baseunit Without Infeed And With F-Di

    BaseUnits for motor starters 4.7 BU30-MS6 BaseUnit without infeed and with F-DI BU30-MS6 BaseUnit without infeed and with F-DI 4.7.1 Product overview Article number 3RK1908-0AP00-0FP0 View Figure 4-11 BaseUnit without 500 V AC infeed, with F-DI BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 91: Connection

    4.7 BU30-MS6 BaseUnit without infeed and with F-DI Properties ● BaseUnit suitable for all fail-safe SIMATIC ET 200SP High Feature motor starters ● The BaseUnit handles the potential group (P1, P2) of the left-hand neighboring module. ● This BaseUnit handles the potential group/infeed bus (500 V AC) of the left-hand BaseUnit and loops this through.
  • Page 92 BaseUnits for motor starters 4.7 BU30-MS6 BaseUnit without infeed and with F-DI Block diagram The following figure shows the block diagram for the BaseUnit without infeed, but with fail- safe input: ① Backplane bus ② Motor starter module ③ Connected power buses 24 V DC, M ④...
  • Page 93: Technical Specifications

    BaseUnits for motor starters 4.7 BU30-MS6 BaseUnit without infeed and with F-DI 4.7.3 Technical specifications Technical specifications of BaseUnit without infeed, with F-DI 3RK1908-0AP00-0FP0 Product type designation BU30-MS6 Galvanic isolation Galvanic isolation between backplane bus and supply voltage Insulation tested with 2500 V AC Rated operating voltage 24 V DC...
  • Page 94 Dimension drawings of I/O modules Dimension drawing BU15-P16+A10+2D, BU15-P16+A10+2B, BU15-P16+A0+12D/T, BU15-P16+A0+12B/T The figure below shows the dimension drawing of the BU15-P16+A10+2D with plugged-in I/O module as an example. Figure A-1 Dimension drawing BU15-P16+A10+2D BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 95 Dimension drawings of I/O modules Dimension drawing BU15-P16+A0+2D, BU15-P16+A0+2B, BU15-P16+A0+2D/T, BU15-P16+A0+2B/T The figure below shows the dimension drawing of the BU15-P16+A0+2D with plugged-in I/O module as an example. Figure A-2 Dimension drawing BU15-P16+A0+2D BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 96 Dimension drawings of I/O modules Dimension drawing BU20-P6+A2+4D, BU20-P6+A2+4B, BU20-P12+A4+0B, BU20-P12+A0+0B, BU20-P12+A0+4B, BU20-P8+A4+0B The figure below shows the dimension drawing of the BU20-P12+A4+0B with plugged-in I/O module as an example. Figure A-3 Dimension drawing BU20-P12+A4+0B BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 97 Dimension drawings of I/O modules Dimension drawing test probe for measurement tap The figure below shows the dimension drawing of a suitable test probe for measurement tap at the BaseUnit. Figure A-4 Dimension drawing test probe BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...
  • Page 98 Dimension drawings of motor starters Dimension drawing BU30-MS1, BU30-MS2, BU30-MS3, BU30-MS4, BU30-MS5, BU30-MS6 The figure below shows the dimension drawing of the BU30-MS-1 with plugged-in motor starter module as an example. Figure B-1 Dimension drawing BU30-MS1 BaseUnits (6ES7193-6BP.../3RK1908-0AP00…) Manual, 12/2016, A5E03727049-AG...