Siemens Simatic ET 200SP Manual page 229

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Measured value data records
E.2 Measured value data record for base measurements (DS 142)
Byte
Measured variable
90...93
Reactive power Qtot L3
94...97
Total reactive power Qtot L1L2L3
98...101
Active power L1
102...105
Active power L2
106...109
Active power L3
110...113
Total active power L1L2L3
114...117
Phase angle L1
118...121
Phase angle L2
122...125
Phase angle L3
126...129
Total apparent energy L1L2L3
130...133
Total reactive energy L1L2L3
134...137
Total active energy L1L2L3
138...141
Total reactive energy inflow L1L2L3
142...145
Total reactive energy outflow L1L2L3
146...149
Total active energy inflow L1L2L3
150...153
Total active energy outflow L1L2L3
154...161
Total apparent energy L1L2L3
162...169
Total reactive energy L1L2L3
170...177
Total active energy L1L2L3
178...185
Total reactive energy inflow L1L2L3
186...193
Total reactive energy outflow L1L2L3
194...201
Total active energy inflow L1L2L3
202...209
Total active energy outflow L1L2L3
210...213
Neutral current
Neutral current
If you operate the AI Energy Meter HF with connection type 3P4W, 3P4W1 or 3P3W, the
neutral current is also calculated under the following conditions:
● Transmission factors of all phase currents (primary and secondary currents) are identical.
● Measured phase currents are greater than the value of the "Low limit for measuring
current parameter.
● The parameter "Reverse current direction" must be the same on all phases.
If one of the conditions is not met, 0 is entered as the value for the neutral current. You can
read the neutral current calculated using measured value data record 142.
228
Data
Unit
type
REAL
var
REAL
var
REAL
W
REAL
W
REAL
W
REAL
W
REAL
°
REAL
°
REAL
°
REAL
VAh
REAL
varh
REAL
Wh
REAL
varh
REAL
varh
REAL
Wh
REAL
Wh
LREAL
VAh
LREAL
varh
LREAL
Wh
LREAL
varh
LREAL
varh
LREAL
Wh
LREAL
Wh
REAL
A
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Value range
-3.0 x 10
... +3.0 x 10
9
9
-3.0 x 10
... +3.0 x 10
9
9
-3.0 x 10
... +3.0 x 10
9
9
-3.0 x 10
... +3.0 x 10
9
9
-3.0 x 10
... +3.0 x 10
9
9
-3.0 x 10
... +3.0 x 10
9
9
0.0 ... 360.0
0.0 ... 360.0
0.0 ... 360.0
0.0 ... 3.4 x 10
38
-3.4 x 10
to +3.4 x 10
38
38
-3.4 x 10
to +3.4 x 10
38
38
0.0 ... 3.4 x 10
38
0.0 ... 3.4 x 10
38
0.0 ... 3.4 x 10
38
0.0 ... 3.4 x 10
38
0.0 ... 1.8 x 10
308
-1.8 x 10
to +1.8 x 10
308
308
-1.8 x 10
to +1.8 x 10
308
308
0.0 ... 1.8 x 10
308
0.0 ... 1.8 x 10
308
0.0 ... 1.8 x 10
308
0.0 ... 1.8 x 10
308
0.0 ... 100000.0
Manual, 07/2018, A5E42674880-AA
Meas-
ured
value
ID
24
38
13
14
15
34
61178
61198
61218
204
206
205
202
203
200
201
214
216
215
212
213
210
211
61149