The following figure shows the value-over-time for two measured values using the example
of a high and low limit as well as the influence of hysteresis and delay time on the counting
of the limit violations.
Figure 9-1
See also
How limit monitoring works (Page 77)
Minimum and maximum values (Page 84)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
Configured limit.
Configured delay time. Is taken into consid-
eration during coming and going.
Hysteresis range. Only considered for out-
going.
Value-over-time for which the limit is moni-
tored.
Edge change. Counter for limit violations is
incremented by 1. If parameterized, a hard-
ware interrupt is triggered.
Influence of hysteresis and delay time on the limit
9.2 Influence of hysteresis and delay time on limit monitoring
Signal wave
Limit monitoring with hysteresis and delay
time
Limit monitoring with hysteresis, but without
delay time
Limit monitoring without hysteresis, but with
delay time
Limit monitoring without hysteresis and
delay time
Limit monitoring