Siemens Simatic ET 200SP Manual page 107

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Parameters
13.2 Description of parameters
Nominal value voltage [V]
Enter the nominal value for the voltage. This is the "operating point" in your application.
Tolerance factor overvoltage/undervoltage [0.1%]
Enter the tolerance factor overvoltage/undervoltage here in increments of 0.1%. You can find
additional information under Diagnostics: Overflow/underflow (Page 114).
Voltage transformer primary voltage [V]
Enter the nominal value for the primary voltage of the voltage transformer used. The
transformer ratio is calculated from the primary and secondary voltage.
Voltage transformer secondary voltage [V]
Enter the nominal value for the secondary voltage of the voltage transformer used. The
transformer ratio is calculated from the primary and secondary voltage.
Limits
Number of limits
Enter the number of measured values that you want to monitor for limits.
Limit monitoring
Enable the monitoring of the limit for a freely definable measured value here. Limit violations
are counted and the count values stored retentively.
Measured variable
Enter the measured value ID (Page 163) that you want to use for limit monitoring.
Enable limit monitoring gate
Enable the limit monitoring gate. When the gate is enabled, the limit monitoring is only
started when the corresponding bit of the associated output user data is set to "1".
Hardware interrupt
Enable the hardware interrupt. The hardware interrupt is triggered if a high or low limit is
violated. Without activation of a hardware interrupt, a limit violation is only displayed in the
user data and in DS 150.