Article number
Diagnostic messages
Line quality
•
Supply voltage
•
Hardware interrupt lost
•
Parameter assignment error
•
Module fault
•
Channel not available
•
Overflow/underflow
•
Overload current
•
Diagnostics indication LED
Monitoring of the supply voltage (PWR-
•
LED)
Channel status display
•
for channel diagnostics
•
for module diagnostics
•
Integrated Functions
Measuring functions
Measuring procedure for voltage meas-
•
urement
Measuring procedure for current measure-
•
ment
Type of measured value acquisition
•
Curve shape of voltage
•
Buffering of measured variables
•
Parameter length
•
Bandwidth of measured value acquisition
•
Measuring range
–
Frequency measurement, min.
–
Frequency measurement, max.
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
6ES7134-6PA00-0CU0
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes; Green LED
Yes; red Fn LED
Yes; green/red DIAG LED
TRMS
TRMS
seamless
Sinusoidal or distorted
Yes
128 byte
3.2 kHz; Harmonics: 63 / 50 Hz, 52 / 60 Hz
45 Hz
65 Hz
Technical specifications
15.1 Technical specifications
135