Siemens Simatic ET 200SP Manual page 209

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

User data variants
Reactive power L1L2L3 (ID 252 or FC
Table D- 4
Reactive power L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Current L2
6 ... 7
Current L3
8 ... 9
Reactive power Qtot L1
10 ... 11
Reactive power Qtot L2
12 ... 13
Reactive power Qtot L3
14 ... 15
Total reactive power Qtot L1L2L3
16 ... 19
Total reactive energy L1L2L3
20
Power factor L1
21
Power factor L2
22
Power factor L3
23
Total power factor L1L2L3
24
Scaling current L1
25
Scaling current L2
26
Scaling current L3
27
Scaling reactive power L1
28
Scaling reactive power L2
29
Scaling reactive power L3
30
Scaling reactive power L1L2L3
31
Scaling total reactive energy L1L2L3
208
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Data
Unit
Value range
type
BYTE
-
252 (FC
BYTE
Bit string
qq xx xx xx
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
INT
1 var
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 var
-27648 ... 27648
DINT
1 varh
-2147483647...
+2147483647
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
Meas-
ured
value
ID
)
-
H
-
66007
66008
66009
66022
66023
66024
66038
222
66019
66020
66021
66037
-
-
-
-
-
-
-
-
Manual, 07/2018, A5E42674880-AA

Hide quick links:

Advertisement

Table of Contents
loading