Active power L1L2L3 (ID 253 or FD
Table D- 3
Active power L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Current L2
6 ... 7
Current L3
8 ... 9
Active power L1
10 ... 11
Active power L2
12 ... 13
Active power L3
14 ... 15
Total active power L1L2L3
16 ... 19
Total active energy L1L2L3
20
Power factor L1
21
Power factor L2
22
Power factor L3
23
Total power factor L1L2L3
24
Scaling current L1
25
Scaling current L2
26
Scaling current L3
27
Scaling active power L1
28
Scaling active power L2
29
Scaling active power L3
30
Scaling active power L1L2L3
31
Scaling total active energy L1L2L3
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Data
Unit
Value range
type
BYTE
-
253 (FD
BYTE
Bit string
qq xx xx xx
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
INT
1 W
-27648 ... 27648
INT
1 W
-27648 ... 27648
INT
1 W
-27648 ... 27648
INT
1 W
-27648 ... 27648
DINT
1 Wh
-2147483647...
+2147483647
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
User data variants
Meas-
ured
value
ID
)
-
H
-
66007
66008
66009
66013
66014
66015
66034
225
66019
66020