Figure A-8
Error while transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for the
parameter data record 128.
Error code in STATUS parame-
ter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E0
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
A.2 Structure of the parameter data record 128 for the entire module
Channel parameter block
Meaning
00
Number of the data record unknown
01
Length of the data record incorrect
00
Slot invalid or cannot be accessed.
01
Incorrect version
02
Error in the header information
Parameter data records
Solution
Enter a valid number for the data record.
Enter a valid value for the data record
length.
Check the station whether the module is
plugged or drawn.
Check the assigned values for the pa-
rameters of the WRREC instruction
Check Byte 0. Enter valid values.
Check bytes 1 to 3, 32, 33, 52, 53, 72
and 73. Correct the length and number of
the parameter blocks.