Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

General reset
With module versions with 20 bytes of output data you can reset some measured values and
counter levels.
An edge change of 0 -> 1 at the bit for the general reset has the following effect:
● Counters for energy, operating hours and limits start at "0" again.
● Results of the power quality analysis are deleted.
● Minimum and maximum value calculation starts again with initial values.
For the general reset, set bit 7 in byte 16 of the output user data. (Page 195)
Figure 6-1
Substitute value behavior
The substitute values for input values of the AI Energy Meter HF amount to "0".
See also
Reading measured values from user data cyclically (Page 50)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
Control byte 16 in the output user data for general reset
Reading and processing measured values
6.1 Basics for reading measured values
43