Siemens Simatic ET 200SP Manual page 99

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Parameters
13.1 Parameters
Parameters
End value energy meter
User data variant
Minimum and maximum value
calculation
Minimum and maximum value
calculation gate
Power quality analysis functions
Residual current analysis
Neutral: Current transformer
primary current [A]
Neutral: Current transformer
secondary current [A]
Voltage dip limit value in relation
to nominal value voltage [0.1%]
Voltage swell limit value in rela-
tion to nominal value voltage
[0.1%]
Threshold overcurrent in relation
to nominal value current [0.1%]
Number of cycles for voltage
swell and dip analysis
Diagnostics power quality
Diagnostics
overflow current
Diagnostics
overflow voltage
Diagnostics
underflow voltage
98
Value range
No end value (infinite counting)
Count periodically to 10
Count periodically to 10
Count periodically to 10
Count periodically to 10
Count periodically to 10
See the table Overview of the user data
variants (Page 205)
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
0 = Disabled
1 ... 99999 = measuring
4294967295 = Calculating
1
5
10 ... 1000
10 ... 10000
10 ... 60000
4 ... 32767
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
No end value (infinite
counting)
3
6
9
12
15
Total power L1L2L3
(W#16#FE)
Disable
Disable
Disable
Disable
0
1
100
100
100
10
Disable
Disable
Disable
Disable
Default setting
Reconfigu-
ration in
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Manual, 07/2018, A5E42674880-AA
RUN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents