Siemens Simatic ET 200SP Manual page 151

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Parameter data records
A.2 Structure of the parameter data record 128 for the entire module
Error code in STATUS parame-
ter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
150
Meaning
01
Reserved bits are not 0.
05
"Voltage measuring range" invalid
20
"Connection type" invalid
21
"User data variant" not possible or input
data configuration not large enough
22
"User data variant" invalid
23
"Line frequency" invalid
29
"Tolerance factor overcurrent in relation to
nominal value current [0.1%]" invalid
2A
"Tolerance time overcurrent" invalid
2B
"Low limit current measurement" in relation
to nominal value current [0.1%] invalid
2C
"Current transformer primary current [A]"
invalid.
2D
"Voltage transformer primary voltage [V]"
invalid
2E
"Voltage transformer secondary voltage [V]"
invalid
2F
"End value energy meter" invalid
30
Invalid data record number.
3E
Only for connection type 3P4W1 and
3P3W1.
Current or voltage transformer parameters
for the different phases are not identical.
3F
"End value for energy meter" or transmis-
sion ratio (primary value, secondary value)
of current and voltage too low.
43
"Current transformer secondary current" for
neutral or all three phases invalid
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Solution
Check bytes 8, 14, 15, 30, 31, 34, 42,
50...53, 54, 62, 70...73, 74, 82, 90...93
and set the reserved bits back to 0.
Check Byte 5. Permitted values: 01
0C
H
Check Byte 4. Permitted values: 00
0B
... 01
H
H
Check Byte 9. Select a different user data
variant or change the configuration.
Check Byte 9. Select a valid code for the
user data variant.
Check Byte 6. Enter valid values.
Check bytes 35, 55 and 75. Enter valid
values.
Check bytes 36...37, 56...57, 67...77.
Enter valid values.
Check bytes 43, 63 and 83. Enter valid
values.
Check bytes 38...41, 58...61, 78...81.
Enter valid values.
Check bytes 46...49, 66...69, 66...69,
88...89. Enter valid values.
Check bytes 38...42 with bytes 58...62
and bytes 78...82 and bytes 44...49 with
bytes 64...69 and bytes 84...89 for iden-
tical values.
Check Bit 4...6 in Byte 6. Enter valid val-
ues.
Check the data record number. Enter a
valid data record number.
Check bytes 38...42 with bytes 58...62
and bytes 78...82 as well as bytes 44...49
with bytes 64...69 and bytes 84...80 for
identical values.
Enter identical values for current trans-
former (secondary current, primary cur-
rent, direction of current) and voltage
transformer (secondary voltage, primary
voltage) at all three phases.
Increase the end value of the energy
meter or the ratio of primary to secondary
current for current transformer and/or
primary to secondary voltage for voltage
transformer.
Check bits 4...5 in bytes 14, 42, 62, 82.
Enter valid values.
Manual, 07/2018, A5E42674880-AA
to
H
,
H